Parameter Meaning
Response to over/underrange
0: relay de-energized
1: relay energized
Input
Sensor connected in 2-wire circuit
Measurement input group 1 on Type: 701050/X1X-1-XX
Measurement input group 2 on Type: 701050/X2X-1-XX
Measurement input group 3 on Type: 701050/X3X-1-XX
Measurement input group 4 on Type: 701050/X4X-1-XX
Start value for indication range with measurement input voltage or current.
Example: input signal (e.g. 4 — 20mA) is to be represented on the display
from -10 to 50. Setting: S.cL= -10 and S.cH=50.
End value for indication range with measurement input voltage or current
Signal for measurement input current: 0 = 0 — 20mA
1 = 4 — 20mA
Value range
from...factory-set...to
0, 1
Pt100:
Pt1000:
KTY2X-6:
or
Fe-Con J:
Fe-Con L:
NiCr-Ni K:
or
0(4)... 20 mA:
/
0 ... 10 V:
/
-999 ... 0... +999
-999 ... 100... +999
0, 1
11