Parameter Meaning
Process value offset
process value offset in °C, °F or digit (no unit)
Lead compensation resistance
This value is used for compensating the resistance of the probe lead for re-
sistance sensors and is dependent on the lead length.
For best temperature measurement results, the resistance value of the
probe lead has to be entered here.
A
If the total resistance at the measurement input (sensor resistance +
selected value for OF.r) exceeds 320
Pt1000/KTY2x-6, a measurement error will occur !
Unit
for the indicated process value
A
For settings in °F, the process value will be converted correspond-
ingly. All other setting, such as for SP, will retain their values.
with Pt100 or 3200
Value range
from...factory-set...to
-99.9 ... 0.0 ... 99.9
0.0 ... 0.0 ... 99.9 in
with
°C, °F or
no (= no unit)