Swegon NIVEAU 3 Manuel De L'utilisateur page 34

Table des Matières

Publicité

CONDUCTOR
ModBus Register W3
Holding register
16 bit integer register
Modbus
Name
4x0059
Not used
4x0060
Not used
4x0061
Not used
4x0062
Not used
4x0063
Manual Temp
4x0064
Manual SA flow
4x0065
Manual EA flow
4x0066
Not used
4x0067
Not used
4x0068
Not used
4x0069
Copy of Coil Status 1-16
ModBus Register W3
Input register
16 bit integer register
Modbus
Name
3x0001
Component Name ID
3x0002 - 0017
Component Name
3x0018
Applacation ID
3x0019
HW Serial No.
3x0020
SW version
3x0021
Not used
3x0022
Application state
3x0023
Not used
3x0024
Not used
3x0025
Time since last boot (Year)
3x0026
Time since last boot
(Hours)
3x0027
Time since last boot
(Minutes)
3x0028
Temp sensor regulator
3x0029
Temp sensor RU1
3x0030
Temp sensor RU2
3x0031
Temp set point RU
3x0032
Flow set point RU
3x0033
Battery level RU
3x0034
Not used
3x0035
Not used
3x0036
Not used
3x0037
Input Analog 1
3x0038
Input Analog 2
3x0039
Input Analog 3
3x0040
Input Analog 4
34
Design déposé. Sous réserve de modifications sans préavis.
R/W
Min/Max
Remarks
10-32
Only used in Manual state (°C)
10/100
Only used in Manual state (%)
10/100
Only used in Manual state (%)
0/65535
"Bit0=0x0001
Bit1=0x0002
...
Bit15=0x0016"
Read only
Min/Max
Remarks
0/10
ID for type of controller in Conductor and Wise system
0/999
Name built of max 16 chr, exch chr (ASCII standard)
0/8
0=Init, 1=Auto Normal, 2=Auto Economy, 3=Auto-
Boost, 4=Manual, 5=TimerFunction 6=Stand-by,
7=Emergency, 8=NightCool
0/8760
After 8760h Year is updated
0/60
After 60min Hour is updated
Scaling 1:10 (°C)
Scaling 1:10 (°C)
Scaling 1:10 (°C)
(°C)
Scaling 1:10 (V)
0/10000
(mV)
0/10000
(mV)
0/10000
(mV)
0/10000
(mV)
20110322
Default
Default
00003
www.swegon.com

Publicité

Table des Matières
loading

Table des Matières