CONDUCTOR
ModBus Register W3
Holding register 16 bit integer register
Modbus
Name
4x0019
Actuator Type Heat
4x0020
Not used
4x0021
Not used
4x0022
Not used
4x0023
Frost guard temperature
4x0024
Economy neutral zone
4x0025
Room temperature
Setpoint
4x0026
Night cool temp set point
4x0027
Timer function time
4x0028
Not used
4x0029
Room unit's min set point
4x0030
Room unit's max set point
4x0031
Room unit's min air flow
4x0032
Room unit's max air flow
4x0033
Boost temp. positive
hysteresis
4x0034
Boost temp. negative
hysteresis
4x0035
RU back to auto state
4x0036
Normal flow SA
4x0037
Normal flow EA
4x0038
Economy flow SA
4x0039
Economy flow EA
4x0040
Night cool flow SA
4x0041
Night cool flow EA
4x0042
Boost flow SA
4x0043
Boost flow EA
4x0044
Timer flow SA
4x0045
Timer func flow EA
4x0046
Stand-by flow EA
4x0047
Stand-by flow EA
4x0048
P term Heat
4x0049
I term Heat
4x0050
P term Cool
4x0051
I term Cool
4x0052
P term Change over
4x0053
I term Change over
4x0054
SA 0% value
4x0055
SA 100% value
4x0056
EA 0% value
4x0057
EA 100% value
4x0058
Not used
Design déposé. Sous réserve de modifications sans préavis.
R/W
Min/Max
Remarks
1/2
1=24VAC, 2=0-10V
5/15
0/10
Ex 4=±2 (°C)
10/32
(°C)
10/20
(°C)
1/300
Boost time when occupancy occurs in room (minutes) 5
0/20
only when room unit is manual state (°C)
25/50
only when room unit is manual state (°C)
5/50
only when room unit is manual state (%)
50/100
only when room unit is manual state (%)
1/10
Room temp rise from defined setpoint,
Auto Boost activated (°C)
0/10
Room temp fall from defined setpoint,
Auto Boost activated (°C)
0/1200
Time when room unit come back from manual state
to auto (minutes)
0/100
(%)
0/100
(%)
0/100
(%)
0/100
(%)
50/100
(%)
50/100
(%)
0/100
(%)
0/100
(%)
0/100
(%)
0/100
(%)
0/100
(%)
0/100
(%)
1/10000
1/10000
1/10000
1/10000
1/10000
1/10000
0/5000
5000/10000
0/5000
5000/10000
20110322
Default
1
10
4
22
15
10
32
10
100
2
1
480
50
50
20
20
80
80
90
90
90
90
10
10
4500
3
7000
3
5000
5
0
10000
0
10000
33