Sigfox Smart Building COMFORT - Guide utilisateur / User guide version V1.0.1

2.1.5 Three modes of sending possible

The device can measure the temperature and humidity in a room, save this information and send it in three transmission modes.
Periodic transmission
FR
Periodic sending allows data to be
collected in a specified period of time, to
Definition
be saved and sent on a regular basis for
analysis over time.
EN
I want my device to read the tempera-
Practical
ture and humidity every 20 minutes, this
example of
information is saved and all my backups
use
are sent to me once per hour.
Period of acquisition
= 600 (600x2 = 20 min)
Backup frequency
= 1 (1 backup every 20 min)
Frequency of transmission
= 3 (3 X 20 min = 1 hour)
• Type of alarm T° (S330)
Associated
= 0 (alarm disabled)
configura-
• Type of humidity alarm (S340)
tion
= 0 (alarm disabled)
In the user
Paragraph 2.1.5.01
guide
CAUTION: The information sending capacity will depend on the network used. Here the case considered works with a technology Sigfox.
The complete list of registers can be found in paragraph 3.4.
Period of
Backup frequency = number of
acquisition
readings between each backup
S321=300
S320=2 (x10min = 20 minutes)
(=10min)
Reading/
Backup
Sampling
Transmission over threshold
The sending of a frame on exceeding a
threshold makes it possible to read data
according to a given period and to send
an alarm only if one of the thresholds is
exceeded
I want my device to send me an alarm
when 24°C in my room is exceeded with
a reading every 10 minutes. I do not
want an alarm for humidity.
Period of acquisition
(S321)
= 300 (300x2 = 10 minutes)
(S320)
Frequency of transmission
= 0 (no periodic sending)
(S301)
• High threshold definition (S331)
= 240 (+24°C)
• Type of alarm T° (S330)
= 1 (high threshold)
• high threshold hysteresis (S330)
= 20 (2°C) My room will have returned
to the "normal" temperature below
22°C.
• Type of humidity alarm (S340)
= 0 (alarm disabled)
Paragraph 2.1.5.02
number of backups (logs) between each sending
Sending/
Transmission
DISTRIBUTED BY TEXIM EUROPE
Periodic transmission and over
Mix of the two modes in order to be able
to reading regularly to receive alerts if
the threshold is exceeded and to save
the information regularly to make the
analysis over time.
I want my device to run every 10
minutes. I want the data saved every 20
minutes and the information sent to me
once per hour.
If the temperature exceeds 24°C I want
an alarm sent to me. I do not want an
alarm for humidity.
Period of acquisition
(S321)
= 300 (300x2 = 10 minutes)
(S301)
Backup frequency
= 2 (2 x 600 sec = 20 min)
Frequency of transmission
= 3 (3 X 20 min = 1 hour)
• High threshold definition (S331)
= 240 (+24°C)
• Type of alarm T° (S330)
= 1 (high threshold)
• high threshold hysteresis (S330)
= 20 (2°C) My room will have returned
to the "normal" temperature below
22°C.
• Type of humidity alarm (S340)
= 0 (alarm disabled)
See schema below.
Frequency of transmission =
S301=3 (x 20 minutes = 1h)
threshold
(S321)
(S320)
(S301)
Time
24h
Page
54
of 85