Sigfox MOTION V2 - Guide utilisateur / User guide version V2.0.1

2.1.5 Three transmission modes to meet needs

The device can detect presence in a room, save this information and send it in three transmission modes.
Periodic transmission
Periodic transmission allows data to be
collected in a specified period of time,
Definition
to be saved and sent on a regular basis
for analysis over time.
I want to take a reading of my bright-
ness rate every 20 min and know the
occupancy rate of the room during this
period.
Practical ex-
I want to minimize my number of trans-
ample of use
missions to optimize my autonomy, so
I want to put the maximum number of
readings in each frame without losing
data.
Period of acquisition
= 900 (900 sec x2 = 1800 seconds
i.e. 30 minutes)
Backup frequency
= 1(1 backup every 30min)
Frequency of transmission
= 4 (4x30min = 2 hours)
• Presence alarm (S330)
Associated
= 0 (alarm disabled)
configuration
• Brightness rate alarm (S343)
= 0 (alarm disabled)
In the use
Paragraph 2.1.5.01
CAUTION: The information sending capacity will depend on the network used. Here the case considered works with a technology Sigfox.
Frequency of transmission =
number of backups between each transmission
S301 = 2 X 1 hour = 2 hours
Period of ac-
quisition S321
number of readings between each backup S320 =
= 10min
Reading
Backup
Transmission over threshold
The transmission of a frame over
threshold makes it possible to read
data - according to a given period and
to send an alarm only if one of the
thresholds is exceeded.
I want an alert if it detects a presence in
the room or if there is no more presence
and if the luminosity is less than 20%
(almost off).
Period of acquisition
(S321)
(300x2 sec = 10 minutes)
Frequency of transmission
(S320)
= 0 (no periodic sending)
• Presence alarm (S330)
(S301)
= 1 (alarm activated)
• Type of luminosity alarm (S340)
= 1 (low threshold)
• Low threshold (343)
= 20 (as a percentage)
• Low threshold hysteresis (S344)
= 5 (as a percentage) the alarm is
raised only if the brightness rises by
+ 5% compared to the threshold
Paragraph 2.1.5.02
Backup frequency =
6 x 10min = 1 hour
Sending
Periodic transmission and over
threshold
Mix of the two modes in order to be
able to poll regularly to receive alerts if
the threshold is exceeded and to save
the information regularly to make the
analysis over time.
I want to know the brightness rate of
my room during the day.
For this my product will send me, 12
time by day, every 2 hours, brightness
reading. However, I want to be alerted if
the brightness of my room drops below
20% or if the room is occupied.
Period of acquisition
(S321) = 300
= 300 (300x2 sec =10 min)
(S301)
Backup Frequency
= 6 (6 x 10 min = 1 hour)
Frequency of transmission
= 2 (2 X 1 hour = 2 hours)
• Presence alarm (S330)
= 1 (alarm activated)
• Type of luminosity alarm (340)
= 1 (low threshold)
• Low threshold (343)
= 20 (as a percentage)
• High threshold hysteresis (S330)
= 5 (as a percentage) the alarm is
raised only if the brightness rises by
+ 5% compared to the threshold
See schema below
FR
EN
(S321)
(S320)
(S301)
Time
Page
37
of 46