Sigfox Smart Building COMFORT - Guide utilisateur / User guide version V1.0.1
3.3.1.04
Registers that configure digital input alarm(s)
Register
Size
Description
(bytes)
S380
1
Configuration of the button (Digital
Input 1)
S381
2
Button alarm threshold (Digital
Input 1)
S382
1
Configuration of the terminal block
(Digital Input 2)
S383
2
Terminal alarm threshold (Digital
Input 2)
Encoding
Details
Hexadecimal
Default: 0x41
Min/max: <7:4> Debounce time 0: No debounce time
1: 10 ms
2: 20 ms
3: 50 ms
4: 100 ms
5: 200 ms
6: 500 ms
7: 1 s
8: 2 s
9: 5 s
A: 10 s
B: 20 s
C: 40 s
D: 60 s
E: 5 minutes
F: 10 minutes
< 3:0> Type
0 = OFF
1 = Event ON 2 = Event OFF
3 = Event ON/ OFF
Decimal
Default: 1
Min/max: 1 to 65535
The value 1 equals 1 detection
When the Digital Input 1 detection counter becomes equal
or higher than this threshold, an alarm is triggered
Hexadecimal
Default: 0x0
Min/max: <7:4> Debounce time 0: No debounce time
1: 10 ms
2: 20 ms
3: 50 ms
4: 100 ms
5: 200 ms
6: 500 ms
7: 1 s
8: 2 s
9: 5 s
A: 10 s
B: 20 s
C: 40 s
D: 60 s
E: 5 minutes
F: 10 minutes
< 3:0> Type
0 = OFF
1 = Event ON 2 = Event OFF
3 = Event ON/ OFF
Decimal
Default: 1
Min/max: 1 to 65535
The value 1 equals 1 detection
When the Digital Input 2 detection counter becomes equal
or higher than this threshold, an alarm is triggered
DISTRIBUTED BY TEXIM EUROPE
FR
EN
Page
67
of 85