Minimum Clearances to Combustible
Surfaces
• Minimum clearance to rear wall is 0 inches.
• Minimum clearance to a vertical right or left side wall
extending above cooking surface is 3 inches.
• Minimum clearance to countertop/cabinet on each side
is 0 inches.
• Minimum of 30 inches between top of cooking surface
and bottom of an unprotected wood or metal cabinet.
• 24 inches between cooking surface and protected wood
or metal cabinet above range. Cabinet bottom must be
protected by at least ¼ inch thick millboard with not
less than No. 28 MSG sheet steel, .015 inch thick
stainless steel, .024 inch thick aluminum, or .020 inch
thick copper.
A
J
H
A—30 inches minimum
B— 0 inches
C—30 inches unprotected/24 inches protected minimum
D—13 inches
E—0 inches
F—25 inches maximum
G—36 inches maximum
H—3 inches minimum (Both sides of range)
J—18 inches minimum
Minimum Clearances to Combustible Surfaces
B
D
C
E
F
G
Special Countertop Conditions
Countertops such as ceramic tile tops cause cabinet and
countertop to be higher than 36 inches. Follow instructions
below when countertop is higher than 36 inches.
1. Raise leveling legs to maximum level.
2. Measure from floor to side trim. If measurement is
less than height of countertop floor must be shimmed.
3. Shim floor using a piece of plywood same size as
range opening. Secure plywood to floor. Plywood
must be as secure as original flooring.
4. Install anti-tip bracket(s) and slide range into place.
Electrical Connection Requirements
!
To avoid the risk of serious electrical shock or property
damage, do not cut or remove the third (ground) prong
from the power plug. A 3-wire grounded conductor
system must be used. Relying on the flexible
connector, hard piping or any other part of the gas
supply line as a ground may cause fire, electrical
shock and/or erratic control operation.
Range must be electrically grounded in accordance with
local codes or in the absence of local codes, with the
National Electrical Code, ANSI/NFPA No. 70-Latest
Edition.
In Canada, electrical connections are to made in
accordance with CSA C22.1 Canadian Electrical Code.
All electrical connections are to be made in accordance
with CSA standards Z240.6.1 electrical requirements for
mobile homes.
Use a 120 volt, 60 hertz, 3-prong receptacle protected by
a 15 amp circuit breaker or time delay fuse. A qualified
electrician should confirm the outlet is properly grounded.
If a 2-prong outlet is encountered, range owner must
replace outlet before using range. Do not cut off cord, use
plug adapter or extension cord, or remove grounding plug.
Grounded Plug and Receptacle
6
WARNING