Jøtul F 602 USA Instructions D'installation Et D'utilisation page 27

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Fig. 11
Rear Heat Shield to reduce clearance
Single wall pipe, top exit only
B
A: 21" - (53,5 cm)
B: 11" -( 28 cm)
Fig. 12
Alcove Installation
Double wall pipe and stove heat shield
A: 55" - (140 cm)
B: 15" - (39,5 cm)
C: 21" - (53,5 cm)
D: 48" - (122 cm)
Alcove with rear heatshield
Fig.13
1
A: Min. 96" - (244 cm)
B: Max. 24" - (61 cm)
1
A
Alcove - double wall pipe and
Fig. 14
wall protection
A: 41" - (104 cm)
B: 8" - (20,5cm)
C: 14" - (36 cm)
D: 48" - (122 cm)
Alcove with wall protection
Fig. 15
A: Min. 96" - (244 cm)
B: Max. 48" - (122 cm)
C: Min. 41" - (104 cm)
D: 1" - (2,5 cm)
Parallel installation with wall shield
Fig. 16
Wall shield
• Must be 27" wide
and centered be-
hind the stove.
• Must be 1" off the
wall and 1" off the
floor.
• With single wall
pipe, the shield
must be 49" high
measured off the
floor.
• With double wall
pipe, the shield
must be 37" high
measured off the
floor.
Combustible wall
(Measurements in cm - for Canada)
27

Publicité

Chapitres

Table des Matières
loading

Table des Matières