294
Code
Message
d'alarme
Unicos
0x1227
Process PID 3 sleep mode
AF8C
Unicos
0x1229
DDCS communication
AF80
between thyristor power
controllers is lost
Unicos
0x1230
Follower
AFE7
Unicos
0x1233
Checksum mismatch
Alarmes utilisateur
Code
Message
d'alarme
Unicos
0x1301
AP Warning 1
Unicos
0x1302
AP Warning 2
Unicos
0x1303
AP Warning 3
Unicos
0x1304
AP Warning 4
Unicos
0x1305
AP Warning 5
Alarmes branche 1 DCT880
Code
Message
d'alarme
DCT880 0x2101
Leg 1 Overcurrent
DCT880 0x2102
Leg 1 Mains Overvoltage
DCT880 0x2103
Leg 1 Thyristor Short Circuit
DCT880 0x2104
Leg 1 Thyristor Open Circuit
DCT880 0x2105
Leg 1 Mains Undervoltage
DCT880 0x2106
Leg 1 Internal Semiconductor
Fuse Open Circuit
DCT880 0x2151
Leg 1 Load Loss
Alarme programmable :
36.10 Leg 1 Load Loss
Function
DCT880 0x2152
Leg 1 Partial Load Loss
Alarme programmable :
36.20 Leg 1 Partial Load Loss
Function
DCT880 0x2153
Leg 1 Partial Load Short
Circuit
Alarme programmable :
36.25 Leg 1 Partial Load
Short Function
DCT880 0x2154
Leg 1 Unit Thermal Overload
Dépannage - alarmes et défauts
Informations supplémentaires
réservé
La communication DDCS (fibre optique) entre les
régulateurs de puissance à thyristors est perdue.
−
Vérifier l'état des régulateurs de puissance à
thyristors.
−
Vérifier les réglages dans le groupe 60
Communication DDCS.
−
Vérifier les branchements des câbles à fibre
optique. Si nécessaire, remplacer les câbles à fibre
optique.
Un régulateur de puissance à thyristors esclave a une
alarme.
−
Vérifier le code auxiliaire. Ajouter 2 au code pour
trouver l'adresse du nœud du régulateur de
puissance à thyristors avec une alarme.
−
Éliminer la cause de l'alarme dans le régulateur de
puissance à thyristors esclave.
Informations supplémentaires
réservé
réservé
réservé
réservé
réservé
Informations supplémentaires
Voir page 307.
Voir page 309.
Voir page 309.
Voir page 310.
Voir page 310.
réservé
Voir page 312.
Voir page 313.
Voir page 313.
Voir page 311.