1. Ensure that the used oil fired heater is
positioned horizontally.
2. Correctly attach the parts of the
combustion chamber, see fig. 4 and 6.
3. Open the filling cover and fill the tank with
fuel.
Caution
Only the following oil types may be
used in the stationary used oil fired
heaters:
Automatic transmission oil
Diesel oil
Hydraulic oil
Oil for household use
Note
Install the equipment in the US
according to the following
publications of the National Fire
Protection Association:
NFPA #30: Flammable and
Combustible
Liquids Code
NFPA #31: Oil Burning
Equipment
NFPA #88A: Parking
Structures
NFPA #88B: Repair Garages
NFPA #211: Chimneys,
Fireplaces and Vents
Local codes may require that the
heater is mounted at a minimum
of 8 feet (2.4 m) off the ground.
This is especially the case when
there are possible combustible or
flamable fumes in the room.
Refer to NFPA #88B.
Install the equipment in Canada
according to the following
standard: CSA B139, installation
Code for Oil Burning Equipment.
AT 300-US series
4. Drain condensate from the fuel tank, see
fig. 3 (J).
5. Make sure that the hot air can flow out
freely.
6. Ensure that inflammable materials are at
a sufficient distance from the heater, see
1.4.
7. Ensure there is sufficient ventilation: the
maximum air consumption is 1625 ft
hour.
8. Make sure there is enough height above
the heater: this needs to be at least 4 ft.
40.020.941 - rev. 04 - 2011
Place the heater on a location with
respect to the following:
Possibility of unobstructed, even
heat distribution.
Safe and easy access for
servicing.
Unobstructed passage for shop
vehicles and equipment.
Proper clearances for
combustibles. Refer to the safety
section.
Adequate combustion air per
local codes. The room must be
ventilated to provide sufficient
combustion-air. The maximum air
consumption is 12 USG/h (46 m
h)
Proper installation of the stack.
The structure in which the heater
is located requires the following
minimum dimensions:
height from the point of
location of the heater: 15 feet
(4.5 m).
length and width: 20 feet
(6 m).
floor area: 400 square feet
2
(36 m
)
Possibility to place the heater on
a combustible flooring.
If the heater is installed at an
elevation, a permanent platform,
including stairs and railings, must
be provided to facilitate regular
maintenance.