SAFETY AND CONTROL DEVICE CONNECTOR
+24 Vdc
Accessories power supply positive 24 Vdc, 250 mA
GND
Accessories power supply negative
+ 24 Vdc
Photocells PH1 and PH2 power supply positive; phototest can be selected with parameter tph 24 Vdc, 250 mA
TX PHOTO
EDGE
Safety sensor edge, ON/OFF NC contact or resistive 8K2 between EDGE and EDGE (warning, with dip switch 1 ON the
safety EDGE input is off)
PH2
Photocells (opening), NC contact between PH2 and COM (warning, with dip switch 2 ON the PHOTOCELL 2 safety device
input is off) The photocell is tripped at any time during opening of the automation system, halting operation immediately; the
automation system will continue opening when the contact is restored.
PH1
Photocells (closing), NC contact between PH1 and COM (warning, with dip switch 3 ON the PHOTOCELL 1 safety device
input is off) The photocell is tripped at any time during closing of the automation system, halting operation immediately and
reversing the travel direction
STOP
STOP safety device, NC contact between STOP and COM (warning, with dip switch 4 ON the STOP safety device input is
off)
This input is classified as a safety device; the contact can be deactivated at any time, cutting out the automation system and
disabling all functions, including Automatic Closure
OPEN
OPEN command NO contact between OPEN and COM
Contact for the HOLD-TO-RUN function. The gate OPENS as long as the contact is held down
CLOSE
CLOSE command NO contact between CLOSE and COM
Contact for the HOLD-TO-RUN function. The gate CLOSES as long as the contact is held down
PED
PEDESTRIAN command NO contact between PED and COM
Used to open the gate partially, depending on the software setting
SS
STEPPING command NO contact between SS and COM
Open/Stop/Close/Stop command, or as set in the software
COM
Common for the PH1, PH2, STOP, OPEN, CLOSE, PED and SS inputs
SIGNAL
Antenna - signal -
SHIELD
Antenna - shield -

4.2 - Display during normal operation

In "NORMAL OPERATING MODE", i.e. when the system is powered up normally, the 3-figure LCD display shows the following status messages:
MESSAGES
MEANING
--
Gate closed or switch-on after shutdown
OP
Gate opening
CL
Gate closing
SO
Gate stopped during opening
SC
Gate stopped during closure
HA
Gate stopped by external event
oP
Gate stopped without automatic reclosure
Pe
Gate in pedestrian opening position without automatic reclosure
Gate open with timed reclosure
-tC
Flashing dash counting in progress
Dash replaced by figures 0..9 countdown (last 10s)
Gate in pedestrian opening position with timed reclosure
-tP
Flashing dash counting in progress
Dash replaced by figures 0..9 countdown (last 10s)
L--
Learning started on limit switch (move the gate off the limit switch to continue the learning procedure)
LOP
Learning opening
LCL
Learning closure
In addition, the dots between the figures illustrate the status of the limit switches, as described in greater detail below:
MESSAGES
MEANING
.--
Limit switch CLOSED (one dot in front of the first figure)
t.C
Limit switch OPEN (one dot between the two figures)
SO
No limit switch active (no dots present)
EN