Further information can be found on
www.somfyarchitecture.com
A
PICTURES
[1] LON 4 DC/E Motor Controller WM 220-230 V AC,
wall-mounted version
[2] LON 4 DC/E Motor Controller DRM 220-230 V AC,
DIN-rail version
B
MOUNTING
[1] Choose the optimal location: flat and large surface
or electric cabinet. Close door!
[2] Needed space for the DIN-rail version
1.
Mounted in an electrical cabinet
[3] Mounting of the LON 4 DC/E Motor Controller
[4] Use cable tie
[5] Keep to minimum distance
C
WIRING
[1] Tool for all terminals
[2] Wiring diagram LON 4 DC/E Motor Controller
D
COMMISSIONING
[1] Check the correct running direction of the end pro-
ducts (group and local control inputs)
UP: end products move upwards (C + ▲)
STOP: end products stop (C + ▼+ ▲)
DOWN: end products move downwards (C + ▼)
 To close window press UP,
to open window press DOWN
Correct the wiring if the running directions are incorrect.
[2] Push buttons
1.
Smoove IB, ref. 1811272
2.
Double push button unlocked
[3] Attach the Motor Controller address label in ac-
cordance with the motor output in a plan or a list
[4] Reset / Prog button: Factory reset of the LON Motor
Controller.
VERDRAHTUNG KABELING WIRING
Anschluss an ...
Forbindelse til ...
Connection to ...
Motors
Switches
Group control
LON bus
220-230 V C
Leitung
Kabel
Cable
Min.: 3 x 0.6 mm/22 AWG
Max.: 3 x 2.5 mm
/14 AWG
2
Min.: 3 x 0.6 mm/22 AWG
Max.: 3 x 2.5 mm
/14 AWG
2
Min.: 3 x 0.6 mm/22 AWG
Max.: 3 x 1.5 mm
/16 AWG
2
2 x 0.8 mm/20 AWG
Min.: 2 x 1.5 mm
/16 AWG
2
Max.: 2 x 2.5 mm
/14 AWG
2
E
CONFIGURATION/ERROR MONITORING
[1] Mode selection DC or DCE
Default mode is DCE!
Type of motors which can be controlled are DC or
DCE (when a LW25-E83 motor is used; it is identifi-
able with 3 wires).
1.
To toggle between modes, give a short press
on the Reset/Prog button. Repeat this until the
desired LED lights up.
Using an unauthorised functional mode can
damage the motors! The mode can be specified
only for all 4 motor outputs.
[2] Error monitoring 
1.
LED flashes red:
short circuit/interruption motor cable
LED flashes yellow:
motor speed can not be reached
2.
LED's show the concerned motor output
If you do not use Somfy motors please follow
the additional information in our detailed ins-
tallation guide (www.somfy.com).
Verdrilltes Adernpaar
Parsnoet
Twisted Pair
Recommended
Recommended
Required, following LON topology guidelines,
www.lonmark.org
animeo LON 4 DC/E MOTOR CONTROLLER. REF. 5126138 A -
Max. Länge
Maks. længde
Max. length
20 m/66 ft
100 m/330 ft
50 m/165 ft
-
6/16