Mounting and securing
6.9
Positioning the function saveguard of the integrated closing sequence control
1.
Pull out driver as far as possible (
X
Loosen screws of stop rod (max. ½ rotation) (
X
Stop rod may not pass under driver.
Pull out stop rod (
X
Distance between edge block and stop is approx. 30 mm
Close moving leaf (
X
Stop rod for function safeguard of the integrated closing sequence control is in position.
Open moving leaf (
X
Tighten screws of stop rod (
X
6. 1 0
Adjusting free swing door closer
1
Adjustment closer size
2
Adjustment closing speed
3
Adjustment latching action
4
Cover cap
5
Slide plate
Adjust closing force (1) to match the door width.
X
Set closing speed (2) and latching action (3).
X
Clip on cover cap (4) and slide plate (5).
X
In accordance with EN directive for fire protection doors, the door closer must be
à
set at least to size EN 3.
Adjustment of closing speed in accordance with EN 1154 (closing time approx. 5 s
à
from 90° open position).
Smooth-moving door must be completely closed by the closer!
à
GB 7
3.
1.).
3.).
4.).
5.).
6.).
(~½
)
2.
GF
6.
2.).
Closer size
2
3
4
5
TS 5000 ISM EFS
4.
4.
5.
Fig.: 6.9.1
Fig.: 6.10.1
Leaf width a [mm]
bis 850
850 - 950
950 - 1100
1100 - 1250
Sec