PERFORMANCES et CARACTERISTIQUES TECHNIQUES
PERFORMANCES and TECHNICAL DATA
LEISTUNG und TECHNISCHE DATEN
APPLICATION MOYENNE TEMPERATURE
ECARTEMENT D'AILETTES : 6,3 mm
MODELE
MODEL
MODELL
SOLO50 146D
1 x Ø 500 / 4PH
SOLO50 166D
1 x Ø 500 / 4PH
SOLO60 146E
1 x Ø 630 / 4PH
SOLO50 186D
1 x Ø 500 / 4PH
SOLO50 246D
2 x Ø 500 / 4PH
SOLO60 166E
1 x Ø 630 / 4PH
SOLO60 186E
1 x Ø 630 / 4PH
SOLO80 146F
1 x Ø 800 / 6PH
SOLO50 266D
2 x Ø 500 / 4PH
SOLO50 346D
3 x Ø 500 / 4PH
SOLO60 246E
2 x Ø 630 / 4PH
SOLO50 286D
2 x Ø 500 / 4PH
SOLO80 166F
1 x Ø 800 / 6PH
SOLO50 366D
3 x Ø 500 / 4PH
SOLO50 446D
4 x Ø 500 / 4PH
SOLO60 266E
2 x Ø 630 / 4PH
SOLO80 186F
1 x Ø 800 / 6PH
SOLO60 346E
3 x Ø 630 / 4PH
SOLO50 386D
3 x Ø 500 / 4PH
SOLO60 286E
2 x Ø 630 / 4PH
SOLO50 466D
4 x Ø 500 / 4PH
SOLO80 246F
2 x Ø 800 / 6PH
SOLO60 446E
4 x Ø 630 / 4PH
SOLO60 366E
3 x Ø 630 / 4PH
SOLO50 486D
4 x Ø 500 / 4PH
SOLO60 386E
3 x Ø 630 / 4PH
SOLO80 266F
2 x Ø 800 / 6PH
SOLO60 466E
4 x Ø 630 / 4PH
SOLO80 346F
3 x Ø 800 / 6PH
SOLO80 286F
2 x Ø 800 / 6PH
SOLO60 486E
4 x Ø 630 / 4PH
SOLO80 366F
3 x Ø 800 / 6PH
SOLO80 446F
4 x Ø 800 / 6PH
SOLO80 386F
3 x Ø 800 / 6PH
SOLO80 466F
4 x Ø 800 / 6PH
SOLO80 486F
4 x Ø 800 / 6PH
(1) Conditions :
Fluide = R404A
Température d'entrée d'air = 0°C
Température d'évaporation = -8°C
Température de liquide = 30°C
(2) La projection d'air indiquée est valable sous la condition
isothermique 20°C et évaporateur collé au plafond.
Les résultats obtenus sur le lieu de l'installation peuvent
être différents par rapport aux valeurs du catalogue, du
fait de la géométrie de la chambre, du chargement de
la chambre, de l'emplacement de l'évaporateur, de la
formation de givre sur l'évaporateur, et de la différence de
température air soufflé-air ambiant.
Vitesse résiduelle de 0,5 m/s.
12
MEDIUM TEMPERATURE APPLICATION
FIN SPACING : 6,3 mm
kW
m³/h
m
7,2
7973
39
9,7
7407
38
10,9
12128
62
11,6
7073
37
14,5
15945
41
14,9
11697
61
17,5
11067
60
19,1
20921
53
19,4
14813
40
21,8
23918
43
21,9
24255
64
23,4
14146
39
25,8
19831
52
29,1
22220
42
29,2
31891
45
30
23394
63
30,7
18623
51
33
36383
66
34,6
21218
41
35,2
22134
62
37,9
29627
44
38,2
41843
55
42,8
48510
68
43,8
35091
65
46,4
28291
43
50,8
33201
64
51,8
39663
54
57,1
46788
67
57,6
62764
57
60,1
37246
53
69,9
44268
66
75,5
59494
56
75,8
83685
59
91,6
55868
55
96,4
79325
58
117,8
74491
57
(1) Conditions:
Fluid = R404A
Inlet air temperature = 0°C
Evaporating temperature = -8°C
Liquid temperature = 30°C
(2) The air throw indicated is valid under the isothermal
condition of 20°C and cooler under the roof.
The results obtained on the place of the installation can
differ from the catalog values,
due to the geometry of the room, loading of
the room, the place of the cooler, the formation of frost
on the cooler, and the difference temperature between
ambient air - blown air.
Residual rate of 0.5 m / s.
m
3m dB(A)
m²
L x h / mm
29
60
29
1509 x 1000
28
60
43
1509 x 1000
48
61
43
1709 x 1162
27
60
57
1509 x 1000
31
62
57
2310 x 1000
47
61
64
1709 x 1162
46
61
85
1709 x 1162
-
58
77
1908 x 1646
30
62
85
2310 x 1000
33
64
85
3112 x 1000
50
63
85
2710 x 1162
29
62
113
2310 x 1000
-
58
115
1908 x 1646
32
64
128
3112 x 1000
35
65
114
3913 x 1000
49
63
128
2710 x 1162
-
58
153
1908 x 1646
52
65
128
3712 x 1162
31
64
170
3112 x 1000
48
63
170
2710 x 1162
34
65
170
3913 x 1000
-
61
153
3110 x 1646
54
66
170
4713 x 1162
51
65
192
3712 x 1162
33
65
227
3913 x 1000
50
65
255
3712 x 1162
-
61
230
3110 x 1646
53
66
255
4713 x 1162
-
62
230
4312 x 1646
-
61
306
3110 x 1646
52
66
340
4713 x 1162
-
62
344
4312 x 1646
-
63
306
5513 x 1646
-
62
459
4312 x 1646
-
63
459
5513 x 1646
-
63
612
5513 x 1646
(1) Bedingungen:
Kältemittel = R404A
Lufteintrittstemperatur = 0 °C
Verdampfungstemperatur = -8 °C
Flüssigkeitstemperatur = 30 °C
(2) Die angegebene Wurfweite ist gültig bei der
Betriebsbedingung von 20 ° C Raumtemperatur und
Verdampfer unter der Obergrenze.Die am Einsatzort
desVerdampfers erzielten Ergebnisse können von den
Katalogwerten abweichen, bedingt durch die Geometrie
des Raumes, Beschickung des Raumes, der Montageort des
Verdampfers, die Eisbildung von im wärmetauscherpaket
und die Temperaturdifferenz zwischen der Ansaug- und der
Ausblasluft. Restgeschwindigkeit von 0,5 m / s.
NORMALKÜHLBEREICH
LAMELLENABSTAND 6,3 mm
kg
110
E
120
E
146
E
128
D
174
E
159
D
172
D
211
E
193
E
274
E
239
E
210
D
235
D
284
E
305
E
265
D
258
D
333
E
292
D
292
D
342
E
352
E
427
E
371
D
376
D
412
D
400
D
478
D
494
E
446
D
532
D
566
D
633
E
635
D
730
D
822
D