RS 485-IS Coupler, 6ES7972-0AC80-0XA0, as of product state 01
Product Information
This product information leaflet contains important information on the RS 485-IS coupler.
Further information
Further Information on the coupler is provided in the
Manual Distributed I/O Device ET 200iSP, (6ES7152-1AA00-8BA0).
Manual Automation Systems Principles of Intrinsically-Safe Design (A5E00206201).
Internet:
http://www.siemens.com/automation/service&support
Manufacturing site
Siemens AG, Industry Sector, Postfach 1963, D-92209 Amberg
Certification
ATEX
II 3 (2) G Ex nA [ib Gb] IIC T4 Gc;
KEMA 03 ATEX 1183X
IECEx
IECEx KEM 05.0016X
Ex nA [ib Gb] IIC T4 Gc
UL-BR 12.0050X
BR
OCP-0029
Note
The RS 485-IS coupler can be used as a device category 3G PROFIBUS node in hazardous
zone 2 areas. Intrinsically safe electrical equipment for device categories 2G and 3G and for
zones 1 and 2 can be connected.
Maintenance
The RS 485-IS coupler is maintenance-free. If problems occur, please contact your local Siemens office:
http://support.automation.siemens.com/WW/view/en/16604999
Installation
The RS 485-IS coupler should be installed inside the hazardous area of the hazardous area (zone 2)
in a suitable housing that provides at least IP 54 protection. The ambient conditions also have to be
taken into account. There must be a manufacturer's declaration for zone 2 available for the housing
(in accordance with EN 60079-15).
If a temperature of > 70 °C is reached in the cable or at the cable entry of this housing under
operating conditions, or if a temperature of > 80 °C can be reached at the junction of the conductors
under operating conditions, the temperature-related properties of the cables must correspond to the
temperatures actually measured.
Commissioning
Only field devices which are certified for the PROFIBUS RS 485-IS interface may be connected to the
RS 485-IS coupler.