Mounting and fixing
6.9
Adjusting trigger unit
Close fixed leaf.
X
Turn regulating screw R until the
X
triangle on the door closer covers the
marking (2.).
Tighten lock nut K.
X
If the physical conditions are unfavour-
X
able (e.g. lintel lining bracket mount-
ing), the trigger unit can be set via the
adjustment piece (14).
Operate the trigger lever several times
X
and check if the marker at the shutter
still is congruent. Readjust if necessary.
Check, if the wire rope mantle fits the
X
adjustment piece SF when the fixed leaf
is open.
6. 1 0 Adjusting electrical hold-open device
Moving leaf is shown.
Open door leaf to desired hold-open angle and fix it there (1.).
X
Remove cable protection foils from guide (2.).
X
Loosen clamping screws of electrical hold-open device (3.).
X
Move electrical hold-open device until catch contacts sliding block (4.).
X
Screw down electrical hold-open device securely (5.).
X
To prevent loops from forming, tighten cable and fasten cable protection at hold open device end (6.).
X
Stow away (7.) loose cable in the cable protection and free area.
X
Secure exposed cable with the cable protection film (8.).
X
CAUTION!
Check free upward movement of the rocker!
X
9.
If necessary, the holding force can be adjusted (9.). According to EN 1155, the release torque should
amount to 40 Nm - 120 Nm for a door with 90° hold- open angle.
GB 8
TS 5000 L-E-ISM VPK
Fig.: 6.9.1
Fig.: 6.10.1