GE AF-600 FP Guide Rapide page 35

Masquer les pouces Voir aussi pour AF-600 FP:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

Specifications
Max. resistor load to common at analog output
Accuracy on analog output
Resolution on analog output
The analog output is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
Control card, RS-485 serial communication:
Terminal number
Terminal number 61
The RS-485 serial communication circuit is functionally seated from other central circuits and galvanically isolated from the
supply voltage (PELV).
Digital output:
Programmable digital/pulse outputs
Terminal number
Voltage level at digital/frequency output
Max. output current (sink or source)
Max. load at frequency output
Max. capacitive load at frequency output
Minimum output frequency at frequency output
Maximum output frequency at frequency output
Accuracy of frequency output
Resolution of frequency outputs
8
8
1) Terminal 27 and 29 can also be programmed as input.
The digital output is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
Control card, 24 V DC output:
Terminal number
Max. load
The 24 V DC supply is galvanically isolated from the supply voltage (PELV), but has the same potential as the analog and digital
inputs and outputs.
Relay outputs:
Programmable relay outputs
Relay 01 Terminal number
Max. terminal load (AC-1)
Max. terminal load (AC-15)
Max. terminal load (DC-1)
Max. terminal load (DC-13)
Relay 02 Terminal number
Max. terminal load (AC-1)
Max. terminal load (AC-15)
Max. terminal load (DC-1)
Max. terminal load (DC-13)
Max. terminal load (AC-1)
Max. terminal load (AC-15)
Max. terminal load (DC-1)
Max. terminal load (DC-13)
Min. terminal load on 1-3 (NC), 1-2 (NO), 4-6 (NC), 4-5 (NO)
Environment according to EN 60664-1
1) IEC 60947 t 4 and 5
The relay contacts are galvanically isolated from the rest of the circuit by reinforced isolation (PELV).
2) Overvoltage Category II
3) UL applications 300V AC 2A
34
AF-600 FP Quick Guide
1)
on 1-3 (NC), 1-2 (NO) (Resistive load)
(Inductive load @ cosφ 0.4)
1)
1)
on 1-2 (NO), 1-3 (NC) (Resistive load)
1)
(Inductive load)
1)
on 4-5 (NO) (Resistive load)
on 4-5 (NO) (Inductive load @ cosφ 0.4)
1)
1)
on 4-5 (NO) (Resistive load)
1)
on 4-5 (NO) (Inductive load)
1)
on 4-6 (NC) (Resistive load)
on 4-6 (NC) (Inductive load @ cosφ 0.4)
1)
1)
on 4-6 (NC) (Resistive load)
1)
on 4-6 (NC) (Inductive load)
2)3)
overvoltage category III/pollution degree 2
DET-759A
500 Ω
Max. error: 0.8% of full scale
8 bit
68 (P,TX+, RX+), 69 (N,TX-, RX-)
Common for terminals 68 and 69
27, 29
0–24 V
40 mA
1 kΩ
10 nF
0 Hz
32 kHz
Max. error: 0.1% of full scale
12 bit
12, 13
200 mA
1-3 (break), 1-2 (make)
240V AC, 2A
240V AC, 0.2A
60V DC, 1A
24V DC, 0.1A
4-6 (break), 4-5 (make)
400V AC, 2A
240V AC, 0.2A
80V DC, 2A
24V DC, 0.1A
240V AC, 2A
240V AC, 0.2A
50V DC, 2A
24V DC, 0.1A
24V DC 10mA, 24V AC 2 mA
2
1)
2

Publicité

Table des Matières
loading

Table des Matières