GE AF-600 FP Guide Rapide page 16

Masquer les pouces Voir aussi pour AF-600 FP:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

Start Up and Functional Tes...
4.2 Applying Power to the Drive
WARNING
HIGH VOLTAGE!
Adjustable frequency drives contain high voltage when
connected to AC line power. Installation, startup and
maintenance should be performed by qualified personnel
only. Failure to perform installation, startup and
maintenance by qualified personnel could result in death
or serious injury.
WARNING
UNINTENDED START!
When drive is connected to AC line power, the motor may
start at any time. The drive, motor, and any driven
equipment must be in operational readiness. Failure to be
in operational readiness when the drive is connected to AC
line power could result in death, serious injury, equipment,
or property damage.
1.
Confirm input voltage is balanced within 3%. If
not, correct input voltage imbalance before
proceeding. Repeat procedure after voltage
correction.
2.
Ensure optional equipment wiring, if present,
matches installation application.
3.
Ensure that all operator devices are in the OFF
position. Panel doors closed or cover mounted.
4.
Apply power to the unit. DO NOT start the drive
at this time. For units with a disconnect switch,
turn to the ON position to apply power to the
drive.
4.3 Basic Operational Programming
Drives require basic operational programming prior to
running for best performance. Basic operational
programming requires entering motor-nameplate data for
the motor being operated and the minimum and
maximum motor speeds. Enter data in accordance with the
following procedure. Parameter settings recommended are
intended for start up and checkout purposes. Application
settings may vary.
Enter data with power ON, but prior to operating the
drive.
1.
Press [Quick Menu] on the keypad.
2.
Use the navigation keys to scroll to Quick Start
and press [OK].
AF-600 FP Quick Guide
3.
4.
5.
6.
7.
8.
This concludes the quick set-up procedure. Press [Status]
to return to the operational display.
In P-04 Auto Tune select Reduced Auto Tune or Full Auto
Tune and follow on-screen instructions. See 4.4 Auto Tune
DET-759A
Select language and press [OK]. Then enter the
motor data in parameters P-02, P-03, P-06, P-07,
F-04 and F-05 (induction motors only, for PM
motors, skip these parameters for now). The
information can be found on the motor
nameplate. The entire quick menu is shown in
P-07 Motor Power [kW] or P-02 Motor
Power [HP]
F-05 Motor Rated Voltage
F-04 Base Frequency
P-03 Motor Current
P-06 Base Speed
F-07 Accel Time 1 is recommended as 60 seconds
for fans or 10 seconds for pumps.
F-08 Decel Time 1 is recommended as 60 seconds
for fans or 10 seconds for pumps.
For F-10 enter Elec OL Trip 1 for Class 20
overload protection. For further information,
please see 3.4.1 Requirements
For F-16 Motor Speed Low Limit [Hz] enter the
application requirements. If these values are
unknown at this time, the following values are
recommended. These values will ensure initial
drive operation. However, take any precautions
necessary to prevent equipment damage. Make
sure that the recommended values are safe to
use for functional testing before starting the
equipment.
Fan = 20 Hz
Pump = 20 Hz
Compressor = 30 Hz
In F-15 Motor Speed High Limit [Hz] enter the
motor frequency from F-04 Base Frequency.
4
4
15

Publicité

Table des Matières
loading

Table des Matières