STEP 3: Mount the drive
Ambient temperature operating range:
- 20 °C to 60 °C (- 4 °F to 140 °F).
Output current derating may be required at ambient temperatures > 40 °C (104 °F). Refer to the Power Installation
Guide (section 5.1). For UL installations, the maximum ambient temperature permitted is 50 °C (122 °F) with any
specified derating applied.
Drives can be panel mounted with 0 mm space between them. A minimum clearance of 100 mm (3.94 in)
is required above and below the drive. Refer to section 3.4 in the Power Installation Guide for information on
derating for reduced clearances.
100 mm (3.94 in)
0 mm
100 mm
(3.94 in)
Frame
H
Mounting
143 mm
1
(5.7 in)
194 mm
2
(7.63 in)
215 mm
3
(8.46 in)
265 mm
4
(10.43 in)
A Drill template for wall mounting is included on the drive packaging (shown below).
STEP 4: Fit cable ground bracket
The cable bracket helps you to organise the cables once they have been connected to the drive.The bracket is
used to clamp the shield of the cables to facilitate EMC compliance (refer to Figure 7-1).
Unidrive M400 Step By Step Guide
Issue Number: 2
The Drive can be screwed onto a backplate or mounted on a DIN rail (size 1 and 2 only).
If you choose to mount it on a rail use 2 screws to secure the drive to the back plate.
W
Overall
Mounting
160 mm
53 mm
(6.3 in)
(2.08 in)
205 mm
55 mm
(8.07 in)
(2.17 in)
226 mm
70.7 mm
(8.9 in)
(2.80 in)
277 mm
86 mm
(10.9 in)
(3.40 in)
+
+
D
Overall
Overall
75 mm
130 mm
(2.95 in)
(5.1 in)
75 mm
150 mm
(2.95 in)
(5.9 in)
90 mm
160 mm
(3.54 in)
(6.3 in)
115 mm
175 mm
(4.5 in)
(6.9 in)
+
+
Weight
Ø
Diameter
5 mm
0.75 kg
(0.2 in)
(1.65 Ib)
5 mm
1.3 kg
(0.2 in)
(3.0 Ib)
5 mm
1.5 kg
(0.2 in)
(3.3 Ib)
6 mm
3.13 kg
(0.23 in)
(6.9 Ib)
3