Connection examples
Lamp not fitted with a neutral conductor
Lamp fitted with a neutral conductor
Connection via two-circuit switch for
manual and automatic operation
Connection via two-way switch for
manual override and automatic operation
Position I: automatic operation
Position II: manual operation
light ON permanently
Note: the unit cannot be switched off, but
operated only at settings I and II.
Functions
The system can be put into operation once the
mains power has been connected and the unit
is closed. Three setting options are concealed
behind the decorative faceplate.
Pressing a programming button sets the
sensor to programming mode.
Reach setting (sensitivity)
(factory setting:
reach approx. 1 m)
1 – 8 m
Twilight setting (response threshold)
(factory setting:
daylight operation
2000 lux)
2 – 2000 lux
PK Elektronik Vertriebs GmbH, E-Mail: info@pkelektronik.com, Internet: www.pkelektronik.com
a) Load, max. illumination 2000 W
(see Technical specifications)
b) Sensor connection terminals
c) Indoor switch
d) Indoor switch, manual, automatic
e) Internal two-way switch, automatic, manual
override
Connecting several high-frequency sensors
in parallel (not illustrated)
In this case, it is important not to exceed the
sensor's maximum connected rating. In add-
ition, all units must be connected to the same
phase.
This means:
- The lamp connected always goes out
- Sensor function is deactivated
- Manual override (if active) is cancelled
The settings may be altered as often as you
wish. The last setting will remain stored in the
memory in the event of power failure.
The sensor's response threshold can be ad-
justed to any reach setting between approx.
1 m and a maximum of approx. 8 m.
Turn adjusting screw
fully anticlockwise for
minimum reach (approx. 1 m), fully clockwise
for maximum reach (approx. 8 m).
The sensor's response threshold can be set to
between approx. 2 lux and 2000 lux.
a) Selecting twilight setting of your choice:
At the light level at which you now want the
sensor to respond to movement and switch on
light, press the
button until the red LED
flashes. This light level will now be stored.
b) Setting night-time operation (4 lux) during
the day
Keep the
button pressed for approx. 5 sec.
until the red LED stops flashing.
12
Functions
Time setting (switch-off delay)
5 sec. – 15 min.
The ON time can be varied continuously be-
tween approx. 5 sec. and a maximum of 15 min.
a) Setting ON time to the accuracy of one
second
- Keep button
pressed until red LED flashes.
- Release button
and wait until chosen ON
time is shown (LED flashes).
- Press button
again until LED goes out.
Your chosen time is now stored to the
accuracy of a second.
- This process is terminated automatically after
the maximum selectable time (15 min.).
- To select the shortest time setting, press
button
twice in brief succession.
Reset function
All settings can be returned to their original
values (daylight operation 2000 lux, light ON
time 5 sec.) whenever you wish.
Operation/Maintenance
The Sensor is suitable for switching on a light
automatically. The unit is not suitable for burg-
lary alarm systems as it is not tamperproof in
the manner prescribed for such systems.
Declaration of conformity
The product complies with the following directives:
Directive 73/23/EEC on low-voltage appliances, as amended
EMC Directive 89/336/EEC, as amended
R & TTE Directive 1999/5/EC, as amended, on
Radio and Telecommunications Terminal Equipment
Herzebrock, October 2004
Ingo Steinel, Management
b) Setting ON time to the accuracy of one
minute
- Keep button
pressed until red LED flashes
(in the lens).
- Release button
, now keep button
pressed until LED goes out and (after 3 sec.)
starts to flash again (slower).
- After the chosen number of flashes (each
LED flash equals 1 min. of light ON time),
re-press button
until LED goes out. Your
chosen time is now stored to the accuracy
of a minute.
- This process is terminated automatically
after the maximum number of flashes
(15 times = 15 min.).
c) Pulse function
The pulse function activates the output for
2 sec. (e.g. for staircase lighting time switches).
To do this, keep button
pressed for approx.
5 sec. until the red LED stops flashing.
To do this, keep both buttons pressed until
the LED comes on and goes out again
(approx. 5 sec.).
The surface can be cleaned with a damp cloth
(without detergents) if dirty.
13