Designation
Line–conducted
interference on AC power
lines
Immunity to interference
on signal lines
Immunity to electrostatic
discharge
Immunity to RF radiation 10 V/m at 80 % amplitude modulation at
Climatic conditions
Temperature
Operation
Storage/transport
Relative humidity
Operation
Storage/transport
Mechanical ambient conditions
Vibration
Operation
Shock
TD 390
C79000–A8576–C292–01
Tables and Technical Data
Technical data
1)
2kV
(to IEC 801–4; burst)
2)
1kV
(to IEC 801–5; s pulse/
line to line)
2)
2kV
(to IEC 801–5; s pulse/
line to ground)
1)
Interference above
1kV can lead to brief
sporadic disturbances (self-recovering)
2)
Only with additional measures, e.g., surge
voltage protector from Dehn, type RZ/E
24 V DC, order no. 917 024
1kV
(to IEC 801–4; burst)
3)
6 kV
Contact discharge
(to IEC 801–2; ESD)
8 kV Air discharge
(to IEC 801–2; ESD)
3)
Discharge above
4kV can lead to brief
sporadic disturbances (self-recovering)
1 kHz, 10 kHz – 80 MHz
(to IEC 801–6)
Tested to DIN IEC 68–2–1,
DIN IEC 68–2–2
0 C to +60 C (32 F to 140 F)
– 20 C to +60 C (4 F to 140 F)
(Max. rate of temperature change 20 C/h
or 36 F/h))
Tested to DIN IEC 68–2–3
5 % to 95 % at 25 C (77 F)
(no moisture condensation)
5 % to 95 % at 25 C (77 F)
(no moisture condensation)
Tested to DIN IEC 68–2–6
10 to 60 Hz, amplitude 0.075 mm
60 to 500 Hz; acceleration 9.8 m/s
Tested to DIN IEC 68–2–27
2
Half–wave: 150 m/s
(15 g), 11 ms
2
A-3