If an activation delay is not activated (Dip 1 / 2 = off / off), switch inputs 1 and 2 can be controlled with a push-button.
For this purpose, the time function must be activated on the respective stage (Dip 7, Dip 8).
The push-button must be pressed for longer than 0.5 sec. If a stage has been activated with the push-button, the cor-
responding stage will automatically deactivate after the overrun time.
10. Overrun
The deactivation of the respective stage, the fan will deactivate after the set overrun time. The length of the overrun
time is adjustable (6, 10, 15, 21 minutes) via DIP-switches 3 and 4.
When switching between the stages, the overrun time is ignored. In case of the simultaneous deactivation of both sta-
ges, the applicable overrun time of the controller can be ignored. As one signal is always technically faster, the reaction
of the controller depends on the last signal.
11. Functional test - test mode:
When applying the supply voltage the fan is in the test mode for 1 minute. (Requirement: Factory setting of DIP-switch,
see wiring diagram SS-1082).
In this case the activation delay and the overrun function is deactivated within the first minute, or for a switching cycle
The humidity detection will remain active in test mode, but will only act as a "push button" during the test minute (hu-
midity activation threshold reached -> immediately on, deactivation threshold reached -> immediately off).