Installation and Operation Instructions
UK
CHAPTER 7
Ansteuerung (Bedarf)
ontrol (demand)
FUNCTION FOR
INSTALLER
N
L
1 2
NOTE
230 V~, 50 Hz
N
L
1 2
WARNING
NOTE
230 V~, 50 Hz
DIP-switch
DIP-Schalter
4
5
6
7
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
----
off
----
----
----
off
----
----
----
on
----
----
----
on
----
----
----
----
off
----
----
----
on
----
----
MiniVent M1/150 F
7.0
Functional description M1/150 F
The fan is activated by the exceedance of the humidity switching threshold or the required ventilation by switching the
switch. The required ventilation is superordinate to the automatic humidity control.
If the humidity sensor is defective, neither automatic mode or required ventilation will work. This ensures that
the defect is detected.
zweitourige Ansteuerung (Bedarf)
1. Terminal allocation
/ 2-speed control (demand)
– Terminal N/L
An operating voltage of 230V is permanently connected to terminals N and L.
Thus the automatic humidity control is fully functional.
– Terminal 1
N
L
Terminal 1 activates stage 1 (required ventilation)
– Terminal 2
Terminal 2 activates stage 2 (required ventilation)
– Both terminals
The latest request will lead
The speed of stages 1 and 2 can be set via the corresponding potentiometer (P1 for stage 1, P2 for stage 2) variably
between 20 % and 100 % of the maximum speed (factory setting stage 1 approx. 70 % and stage 2 approx. 100 %).
The setting then applies for both the required ventilation and the automatic humidity control. However, in order to en
sure sufficient dehumidification, the speed in automatic mode is always at least 50 % in the lower stage and at least
80 % in the higher stage, even with a lower potentiometer setting
WARNING!
The DIP-switch or potentiometer setting can only be changed by a trained electrician. The device must be iso-
L
lated from the mains power supply! The DIP-switch or potentiometer setting can only be effectively changed
N
after reconnecting the mains power supply.
230 V~, 50 Hz
All time specifications may slightly differ due to component tolerances and ambient temperatures.
2. Potentiometer setting
If a higher value is desired based on the factory setting, the potentiometer must be turned up or clockwise. Converse-
ly, the potentiometer must be turned counterclockwise for a lower value. The potentiometer settings are displayed in
the following figure.
Potentiometer
fig.13
rpm / niveau %
8
U/min in %
----
50
70
P1
----
----
----
100
20
----
Klemme,
Stufe
step / niveau 1
----
----
----
----
Zuordnung
Entfeuchtung zur Stufe
----
1 2
L
L
rpm / niveau %
U/min in %
50
70
P2
P3
100
20
1
Klemme,
Stufe
2
Einschaltschwelle
step / niveau 2
- switch-on threshold
- seuil de mise en marche
12
Assignment dehumidification
for level
DSEL 2, 1306.003
0
0
Humidity r.H. %
Feuchte rF %
70
60
80
50
40
90
1) Control mode