Télécharger Imprimer la page
Helios ultra Silince MiniVent M1/150 F Notice De Montage Et D'utilisation

Helios ultra Silince MiniVent M1/150 F Notice De Montage Et D'utilisation

Masquer les pouces Voir aussi pour ultra Silince MiniVent M1/150 F:

Publicité

Les langues disponibles

Les langues disponibles

Liens rapides

Helios Ventilatoren
MONTAGE- UND BETRIEBSVORSCHRIFT
Kleinlüfter
Helios MiniVent
M1/150 F
- mit Feuchtesteuerung
D
NR. 19 066.002
IP 45

Publicité

loading

Sommaire des Matières pour Helios ultra Silince MiniVent M1/150 F

  • Page 1 Helios Ventilatoren MONTAGE- UND BETRIEBSVORSCHRIFT NR. 19 066.002 IP 45 Kleinlüfter Helios MiniVent M1/150 F - mit Feuchtesteuerung...
  • Page 2: Table Des Matières

    DEUTSCH Inhaltsverzeichnis KAPITEL 1. SICHERHEIT ..............Seite 1 1.0 Wichtige Informationen .
  • Page 3: Wichtige Informationen

    Montage- und Betriebsvorschrift MiniVent M1/150 F Wichtige Informationen KAPITEL 1 Zur Sicherstellung einer einwandfreien Funktion und zur eigenen Sicherheit sind alle nachstehenden Vorschriften genau durchzulesen und zu beachten. SICHERHEIT Dieses Dokument ist Teil des Produktes und als solches zugänglich und dauerhaft aufzubewahren um einen sicheren Betrieb des Ventilators zu gewährleisten.
  • Page 4: Personalqualifikation

    Stillstandzeiten, starke Verschmutzung, übermäßige Beanspruchung durch klimatische, technische oder elek- tronische Einflüsse geeignet. Gleiches gilt für die mobile Verwendung der Ventilatoren (Fahr-, Flugzeuge, Schiffe, usw.). Ein Einsatz unter diesen Bedingungen ist nur mit Einsatzfreigabe seitens Helios möglich, da die Serienausführung hier- für nicht geeignet ist.
  • Page 5: Garantieansprüche - Haftungsausschluss

    KAPITEL 2 Alle Ausführungen dieser Dokumentation müssen beachtet werden, sonst entfällt die Gewährleistung. Gleiches gilt für Haftungsansprüche an Helios. Der Gebrauch von Zubehörteilen, die nicht von Helios empfohlen oder angeboten wer- ALLGEMEINE HINWEISE den, ist nicht statthaft. Eventuell auftretende Schäden unterliegen nicht der Gewährleistung. Veränderungen und Um- bauten am Gerät sind nicht zulässig und führen zum Verlust der Konformität, jegliche Gewährleistung und Haftung ist...
  • Page 6: Berührungsschutz

    Montage- und Betriebsvorschrift MiniVent M1/150 F Berührungsschutz - MiniVent M1/150 F Kleinventilatoren werden serienmäßig mit saugseitigem Schutzgitter geliefert. In Abhängigkeit der Ein- bauverhältnisse kann auch druckseitig ein Berührungsschutz erforderlich sein. Entsprechende Schutzgitter sind als Zubehör lieferbar. - Ventilatoren, die durch ihre Einbauweise (z.B. Einbau in Lüftungskanäle oder geschlossene Aggregate) geschützt sind, be- nötigen kein Schutzgitter, wenn die Anlage die gleiche Sicherheit bietet.
  • Page 7: Kapitel 4 Funktion

    Automatikmodus: Die Feuchteautomatik funktioniert auch ohne Anschluss eines Schalters. Bedarfslüftung: Durch den Anschluss von z.B. einem DSEL 2 aus dem Helios Zubehörprogramm können die Stufen 1 und 2 zusätzlich geschaltet werden. Die Bedruckung des Schalters stimmt mit den Funktionen des Lüfters im Aus- lieferungszustand überein.
  • Page 8 Montage- und Betriebsvorschrift MiniVent M1/150 F – Ereignissteuerung (schneller Feuchteanstieg) Bei schnellem Feuchteanstieg (Verursacht z.B. durch Duschen, Baden) wird der Ventilator schon vor Erreichen der eingestellten Schaltschwelle eingeschaltet, um möglichst effektiv die übermäßige Feuchte im Raum zu beseitigen und schnell den Wohlfühlbereich im Raum wieder herzustellen. Beim Erreichen der Ausschaltschwelle schaltet sich der Ventilator nach Ablauf der eingestellten Nachlaufzeit ab.
  • Page 9: Reinigung

    Montage- und Betriebsvorschrift MiniVent M1/150 F 7. Nachlauf Nach dem Abschalten der jeweiligen Stufe schaltet sich der Ventilator erst nach der eingestellten Nachlaufzeit ab. Die Länge der Nachlaufzeit ist einstellbar (6, 10, 15, 21 Minuten). Sie kann für die Bedarfslüftung deaktiviert werden, jedoch nicht im Automatikmodus.
  • Page 10: Lieferumfang/Konstruktiver Aufbau

    Montage- und Betriebsvorschrift MiniVent M1/150 F Alle nachfolgenden Informationen und Anweisungen sind nur für eine autorisierte Elektrofachkraft bestimmt! Lieferumfang/Konstruktiver Aufbau KAPITEL 6 Entnehmen Sie die M1-Liefereinheit erst unmittelbar vor dem Einbau aus dem Karton, um mögliche Beschädigungen und Verschmutzungen beim Transport sowie auf der Baustelle zu vermeiden. INSTALLATION Abb.4 Lieferumfang:...
  • Page 11 Montage- und Betriebsvorschrift MiniVent M1/150 F Abb.5 Abb.6 Empfohlener Kabelführung unter dem Gehäuse. Kabelaustritt beliebig 0...-360 °, ideal jeweils 45° min. 130 mm Möglicher Bohrlöcher Kabelaustritt- bereich 2. Bohrlöcher Gehäuse ansetzen Löcher markieren und abbohren und mit mind. zwei Befestigungsschrauben und Dübeln montieren. 3.
  • Page 12: Elektrischer Anschluss / Inbetriebnahme

    Montage- und Betriebsvorschrift MiniVent M1/150 F Elektrischer Anschluss / Inbetriebnahme ACHTUNG! ACHTUNG Das drehende Laufrad kann Ihre Finger quetschen. Vor dem Inbetriebnehmen Berührungsschutz sicherstellen! WARNUNG! WARNUNG - Der elektrische Anschluss, bzw. die Erstinbetriebnahme darf nur von einer autorisierten Elektrofachkraft ent- sprechend den Angaben in den beiliegenden Anschlussplänen ausgeführt werden.
  • Page 13: Einbau

    Montage- und Betriebsvorschrift MiniVent M1/150 F Abb.9 Abb.10 Œ ˜ 8 mm Œ — – 1. Anschlussraumabdeckung — auf Kunststoffgehäuse - Länge Einzeladern 135 mm - Abisolierlänge 8 mm stecken und festschrauben (Pos Œ) - Mantelleitung bündig mit Kabelkanal abisolieren 2.
  • Page 14: Funktionsbeschreibung M1/150 F

    Montage- und Betriebsvorschrift MiniVent M1/150 F Funktionsbeschreibung M1/150 F KAPITEL 7 Zum Einschalten des Lüfters führt entweder die Überschreitung der Feuchte-Schaltschwelle oder die Bedarfslüftung durch Schalten des Schalters. Die Bedarfslüftung ist der Feuchteautomatik übergeordnet. FUNKTION FÜR INSTALLATEUR Bei defektem Feuchtesensor funktioniert sowohl der Automatikmodus als auch die Bedarfslüftung nicht. HINWEIS Dadurch ist sichergestellt, dass der Defekt bemerkt wird.
  • Page 15 Montage- und Betriebsvorschrift MiniVent M1/150 F 3. Feuchtefunktionen Mit einer Kombination aus Dip-Schalter 6, 7 und 8 kann zwischen einstufiger, zweistufiger und stufenloser Feuchtefunk- tion gewählt werden. Die Wahl der Feuchtefunktion ist technisch an die Zuordnung der Zeitfunktionen zu bestimmten Lüfterstufen gebunden (siehe Tabelle unten).
  • Page 16 Montage- und Betriebsvorschrift MiniVent M1/150 F – Ereignissteuerung (schneller Feuchteanstieg) Bei schnellem Feuchteanstieg (Verursacht z.B. durch Duschen, Baden) wird der Ventilator schon vor Erreichen der eingestellten Schaltschwelle eingeschaltet, um möglichst früh und effektiv die übermäßige Feuchte im Raum zu be- seitigen und schnell den Wohlfühlbereich im Raum wieder herzustellen.
  • Page 17 Montage- und Betriebsvorschrift MiniVent M1/150 F 9. Tasterbetrieb Ist keine Einschaltverzögerung (Dip 1 / 2 = off / off) aktiviert, können die Schalteingänge 1 bzw. 2 mit einem Tasterimpuls angesteuert werden. Dazu muss auf der betreffenden Stufe die Zeitfunktion aktiviert sein (Dip 7, Dip 8). Der Taster muss mehr als 0,5 sec.
  • Page 18: Schaltplanübersicht Für M1/150 F

    - time on level 1 Zeit auf beiden Stufen ---- ---- ---- ---- ---- ---- 2-stufig, klein+groß stufenlos high level, stepped - time on level 2 stepped stepless - time on both levels Auslieferung Helios Serie Factory setting 85337 001 SS-1082 31.07.14...
  • Page 19: Instandhaltung Und Wartung

    Lösung Ventilator startet nicht – keine Spannung Netzspannung prüfen Anschluss nach Schaltplan überprüfen – Feuchtesensor defekt Helios Kundendienst kontaktieren – Laufrad blockiert Blockade lösen, reinigen, ggf. Laufrad ersetzen – Motor blockiert Helios Kundendienst kontaktieren – Motor gerade abgeschaltet Einschaltschutz (15 sec.) abwarten Sicherung löst aus...
  • Page 20: Stilllegen Und Entsorgen

    HELIOS Ventilatoren GmbH + Co KG · Lupfenstraße 8 · 78056 VS-Schwenningen HELIOS Ventilateurs · Le Carré des Aviateurs · 157 av. Charles Floquet · 93155 Le Blanc Mesnil Cedex CH HELIOS Ventilatoren AG · Tannstrasse 4 · 8112 Otelfingen GB HELIOS Ventilation Systems Ltd.
  • Page 21 Helios Ventilatoren INSTALLATION AND OPERATING INSTRUCTIONS NO. 19 066.002 IP 45 Mini fan Helios MiniVent M1/150 F - with automatic humidity control...
  • Page 22 ENGLISH Table of contents CHAPTER 1. SAFETY ..............Page 1 1.0 Important information .
  • Page 23: Important Information

    Installation and Operation Instructions MiniVent M1/150 F Important information CHAPTER 1 In order to ensure complete and effective operation and for your own safety, all of the following instructions should be read carefully and observed. SAFETY This document should be regarded as part of the product and as such should be kept accessible and durable to ensure the safe operation of the fan.
  • Page 24: Application

    The MiniVent M1/150 F mini fans are suitable for conveying normal or slightly dusty (particle size < 10 µm), less aggres- sive and humid air, in moderate climates and in the range of their performance curves, see Helios sales documents / internet.
  • Page 25: Warranty Claims - Exclusion Of Liability

    All versions of this documentation must be observed, otherwise the warranty shall cease to apply. The same applies to liability claims against Helios. The use of accessory parts, which are not recommended or offered by Helios, is not per- GENERAL OPERATING mitted.
  • Page 26: Protection Against Contact

    Installation and Operation Instructions MiniVent M1/150 F Protection against contact - MiniVent M1/150 F mini fans are delivered with an intake-side protection guard as standard. Depending on the mounting conditions, protection against contact may also be required on the discharge side. Corresponding protection guards are avai- lable as accessories.
  • Page 27 Automatic mode: The automatic humidity control also works without the connection of a switch. Required ventilation: For example, by connecting a DSEL 2 from the Helios accessories range, stages 1 and 2 can also be switched. The print on the switch corresponds to the fan functions in the delivery status.
  • Page 28 Installation and Operation Instructions MiniVent M1/150 F – Event control (fast humidity increase) In case of a fast humidity increase (e.g. caused by showering, bathing), the fan will be activated before the set acti- vation threshold is reached, so that the excessive humidity in the room can be removed as effectively as possible and the comfort zone in the room can be restored quickly.
  • Page 29: Cleaning

    Installation and Operation Instructions MiniVent M1/150 F 7. Overrun After the deactivation of the respective stage, the fan will deactivate after the set overrun time. The length of the overrun time is adjustable (6, 10, 15, 21 minutes). It can be deactivated for the required ventilation, but not in automatic mode. When switching between the stages, the overrun time is ignored.
  • Page 30: Scope Of Delivery/Design

    Installation and Operation Instructions MiniVent M1/150 F All subsequent information and instructions are intended solely for authorised electricians! Scope of delivery/Design CHAPTER 6 Leave the M1 delivery unit in its box until installation. Check that the fan is in good condition and has not been damaged in transit.
  • Page 31 Installation and Operation Instructions MiniVent M1/150 F fig.5 fig.6 Recommen- Cable runs under the casing. cable exit optional 0...-360°, ideally in each case 45° min. 130 mm Possible ca- Drill holes ble exit area 2. Drill holes Set casing against the wall, mark the holes and drill. Fasten with at least 2 screws and plugs. 3.
  • Page 32: Electrical Connection / Start-Up

    Installation and Operation Instructions MiniVent M1/150 F Electrical connection / Start-up ATTENTION! ATTENTION The rotating impeller can crush fingers. Ensure protection against contact before starting up! WARNING! WARNING - The electrical connection and initial start-up are to be carried out in accordance with the relevant wiring dia gram and are only to be carried out by a certified electrician.
  • Page 33: Mounting

    Installation and Operation Instructions MiniVent M1/150 F fig.9 fig.10 Œ ˜ 8 mm Œ — – 1. Place and screw terminal compartment cover — on - Length of single conductors 135 mm - Stripping length 8 mm plastic casing (Pos Œ) - Strip sheathed cable flush with cable duct 2.
  • Page 34: Functional Description M1/150 F

    Installation and Operation Instructions MiniVent M1/150 F Functional description M1/150 F CHAPTER 7 Ansteuerung (Bedarf) The fan is activated by the exceedance of the humidity switching threshold or the required ventilation by switching the switch. The required ventilation is superordinate to the automatic humidity control. ontrol (demand) FUNCTION FOR INSTALLER...
  • Page 35 Installation and Operation Instructions MiniVent M1/150 F 3. Humidity functions One-stage, two-stage and variable humidity function can be selected with a combination of DIP-switches 6, 7 and 8. The selection of the humidity function is technically linked to the assignment of time functions to certain fan stages (see table below).
  • Page 36 Installation and Operation Instructions MiniVent M1/150 F In case of a fast humidity increase (e.g. caused by showering, bathing), the fan will be activated before the set acti- vation threshold is reached, so that the excessive humidity in the room can be removed as effectively as possible and the comfort zone in the room can be restored quickly.
  • Page 37 Installation and Operation Instructions MiniVent M1/150 F If an activation delay is not activated (Dip 1 / 2 = off / off), switch inputs 1 and 2 can be controlled with a push-button. For this purpose, the time function must be activated on the respective stage (Dip 7, Dip 8). The push-button must be pressed for longer than 0.5 sec.
  • Page 38: Circuit Diagram Overview For M1/150 F

    - time on level 1 Zeit auf beiden Stufen ---- ---- ---- ---- ---- ---- 2-stufig, klein+groß stufenlos high level, stepped - time on level 2 stepped stepless - time on both levels Auslieferung Helios Serie Factory setting 85337 001 SS-1082 31.07.14...
  • Page 39: Servicing And Maintenance

    Fan does not start – No voltage Check mains voltage Check connection according to circuit diagram – Defective humidity sensor Contact Helios customer services – Impeller blocked Clear blockade, clean, replace impeller if necessary – Motor blocked Contact Helios customer services –...
  • Page 40: Standstill And Disposal

    HELIOS Ventilatoren GmbH + Co KG · Lupfenstraße 8 · 78056 VS-Schwenningen HELIOS Ventilateurs · Le Carré des Aviateurs · 157 av. Charles Floquet · 93155 Le Blanc Mesnil Cedex CH HELIOS Ventilatoren AG · Tannstrasse 4 · 8112 Otelfingen GB HELIOS Ventilation Systems Ltd.
  • Page 41 Helios Ventilateurs NOTICE DE MONTAGE ET D’UTILISATION N° 19 066.002 IP 45 Mini-ventilateur Helios MiniVent M1/150 F - avec hygrostat électronique...
  • Page 42 FRANÇAIS Sommaire CHAPITRE 1. SÉCURITÉ ..............Page 1 1.0 Informations importantes .
  • Page 43: Chapitre 1. Sécurité

    DANGER Des dispositions particulières sont applicables pour l’utilisation, le raccorde- ment et le fonctionnement ; contacter Helios en cas de doute. Veiller à bien res- pecter les normes nationales, règlements de sécurité et instructions. Lors de la manipulation du ventilateur, veiller à bien respecter les règles de sécurité...
  • Page 44: Domaine D'utilisation

    (taille des particules < 10 µm), humide et contenant peu de particules agressives, en climat tempéré et dans la limite des courbes de performance (voir documentation ou site internet Helios). Seule une utilisation est autorisée dans une installation fixe, en intérieur. La température max. ambiante autorisée est 40 °C. Les mini-ventila- teurs M1/150 F MiniVent possèdent un indice de protection 45, classe d’isolation II et doivent être installés dans les...
  • Page 45: Demande De Garantie - Réserves Du Constructeur

    KAPITEL 2 Toute demande de remplacement ou de réparation à titre gratuit sera déclinée en cas de non-respect des indications contenues dans la notice. L’utilisation d’accessoires, non fournis, non conseillés ou non proposés par Helios, est ALLGEMEINE HINWEISE interdite. Si ces consignes ne sont pas respectées, la garantie s’annule. Idem pour les réserves constructeur.
  • Page 46: 2.8 Protection Moteur

    Notice de montage et d’utilisation MiniVent M1/150 F Protection contre tous contacts accidentels - Les mini-ventilateurs MiniVent M1/150 F sont livrés de série avec une grille de protection à l’aspiration. Selon le type d'installation, une grille de protection au refoulement peut être nécessaire : cette grille est disponible en accessoire. - Les ventilateurs installés dans un système déjà...
  • Page 47: Chapitre 4. Fonctionnalités

    Mode automatique : la commande automatique de l’humidité fonctionne aussi sans raccordement d’un interrupteur. Ventilation contrôlée : avec le raccordement d’un DSEL 2 (accessoire Helios) par exemple, les vitesses 1 et 2 peuvent également être changées. La configuration usine du ventilateur correspond à un fonctionnement avec interrupteur 2 vitesses.
  • Page 48 Notice de montage et d’utilisation MiniVent M1/150 F – Régulation réactive (augmentation rapide du taux d’hygrométrie) Lors d’une augmentation rapide du taux d’hygrométrie (par ex. lors de douche ou de bain), le ventilateur s’enclenche avant d’avoir atteint le seuil de mise en route afin d’évacuer rapidement et efficacement l’humidité excessive présente dans la pièce.
  • Page 49: Chapitre 5. Entretien/Démontage

    Notice de montage et d’utilisation MiniVent M1/150 F 7. Minuterie Après la désactivation de chaque vitesse, le ventilateur s’arrête après la durée de temporisation. La durée de la minu- terie est réglable (6, 10, 15, 21 minutes). Elle peut être désactivée pour les débits d’air de pointe, mais pas en mode automatique.
  • Page 50: Chapitre 6. Installation

    Notice de montage et d’utilisation MiniVent M1/150 F Toutes les informations et consignes suivantes sont destinées à un électricien qualifié, certifié et autorisé ! Kit d’utilisation/Montage apparent CHAPITRE 6 Ne déballer qu’au moment de l’installation, afin d’éviter tous dommages et salissures lors du transport ou sur le chantier.
  • Page 51 Notice de montage et d’utilisation MiniVent M1/150 F Fig. 5 Fig. 6 Sortie de Introduction des câbles sous le boîtier câbles conseillée : 0-360 °, angle idéal : 45° min. 130 mm Sortie Percement possible de câbles 2. Percements Positionner la virole, marquer l’emplacement des fixations et percer. Fixer en utilisant au minimum deux vis de fixation avec chevilles.
  • Page 52: Raccordement Électrique / Mise En Service

    Notice de montage et d’utilisation MiniVent M1/150 F Raccordement électrique / Mise en service ATTENTION ! ATTENTION La partie rotative peut pincer vos doigts. Vérifier la protection contre tout contact accidentel avant la mise en service ! AVERISSEMENT ! AVERTISSEMENT - Le raccordement électrique et la première mise en service ne peuvent être effectués que par un électricien agréé...
  • Page 53: Montage

    Notice de montage et d’utilisation MiniVent M1/150 F Fig. 9 Fig. 10 Œ ˜ 8 mm Œ — – 1. Emboîter et visser (Pos Œ) le couvercle du bornier - Longueurs de chaque fils : 135 mm. - Dénuder le fils sur 8 mm. de raccordement —.
  • Page 54: Chapitre 7. Fonctionnalités Pour L'installateur

    Notice de montage et d’utilisation MiniVent M1/150 F Description de la fonctionnalité M1/150 CHAPITRE 7 L'enclenchement du ventilateur se fait soit parce que le seuil d'hygrométrie est dépassé, soit par action sur un interrupteur. L'action manuelle est prioritaire sur l'hygrostat. FONCTIONNALITÉS POUR L’INSTALLATEUR Si la sonde d’hygrométrie est défectueuse, ni le mode automatique, ni le mode manuel ne fonctionnent.
  • Page 55 Notice de montage et d’utilisation MiniVent M1/150 F 3. Fonctionnalités de l’hygrostat Avec la combinaison d’interrupteurs 6, 7 et 8, la fonction hygrostat peut être définie sur 1 vitesse, 2 vitesses ou de façon progressive. Le choix du mode de fonctionnement est lié techniquement à l'affectation des vitesses à la programmation horaire (voir tableau ci-dessous).
  • Page 56 Notice de montage et d’utilisation MiniVent M1/150 F – Régulation réactive (augmentation rapide du taux d’hygrométrie) Lors d’une augmentation rapide du taux d’hygrométrie (par ex. lors de douche ou de bain), le ventilateur s’enclenche avant d’avoir atteint le seuil de mise en route afin d’évacuer rapidement et efficacement l’humidité excessive présente dans la pièce.
  • Page 57 Notice de montage et d’utilisation MiniVent M1/150 F 9. Bouton poussoir Si le démarrage différé est désactivé (DIP 1/2 = off/off), chacune des deux vitesses peuvent être commandées par l’in- termédiaire d’un bouton poussoir. Pour cela, il faut que la programmation soit activée sur la vitesse concernée (DIP 7, DIP 8).
  • Page 58 Notice de montage et d’utilisation MiniVent M1/150 F Schéma de raccordement pour M1/150 F Fig. 14 Marche (forcée) M1/150 F 1 vitesse Fonctionnement automatique Marche (forcée) sans marche forcée Interrupteur 2 vitesses lumière disponible à la vente pour le contrôle 1 vitesse DSEL 2, 1306.003 230 V~, 50 Hz...
  • Page 59: Dysfonctionnements

    Attendre la fin de la protection contre les démarrages intempestifs (15 sec.). Le fusible – court-circuit moteur Appeler le SAV de Helios. déclenche – câble ou raccordement Remplacer des pièces ou le moteur entier (appeler le SAV de Helios). endommagé – mauvais raccordement Vérifier le raccordement, le modifier. Vibrations – encrassement Nettoyer.
  • Page 60: Recyclage

    HELIOS Ventilatoren GmbH + Co KG · Lupfenstraße 8 · 78056 VS-Schwenningen HELIOS Ventilateurs · Le Carré des Aviateurs · 157 av. Charles Floquet · 93155 Le Blanc Mesnil Cedex CH HELIOS Ventilatoren AG · Tannstrasse 4 · 8112 Otelfingen GB HELIOS Ventilation Systems Ltd.