Remarks:
1) These variables are only placeholders and not available in this version. The confi guration of system and transformer ratios
must be done via the keys of the basic device.
2) Depending in the system some measurands are not available (see basic unit A2xx). In this case the value 8.888e+030 will
be output resp. 1.55555 for power factors, to allow clear recognition of this circumstance.
3) Here the interval time for the sending of all variables of the appropriate object (function block) can be set. If this time is set
to 0.0s the time monitoring is switched off.
4) Here the maximum absolute alteration of the variable value since the last transmission can be set. If the value is exceeded
all values of the object are sent again. If the value is set to 0.0 no transmission will take place.
5) These value is calculated locally and is not available in the basic unit A210/A220. Uavg=(U1+U2+U3)/3.
6) If the power factor can't be calculated due to low input signals the value 1.1111 is output.
7) Special variable for summation station U1601.
9. Programming of digital input/output
There are detailed programming instructions in the operating
instructions for the basic instrument A2xx.
Programming of digital output (Type A)
The switching state follows the state of digital output 1 of the
basic unit. The selection of the measurand to monitor at the
limit are set in the basic unit (OUT1). Remark: The output of
energy pulses is not possible.
Programming of digital input (Type E)
Brief instructions
Press
P
> 2 sec.
Press the
P
button, until the menu required, "Digital input"
appears. Enter the parameter level with the
P
Press the
button and change the fl ashing parameter with
the
buttons.
Press
P
> 2 sec. The basic instrument is now in display
mode again.
The module must be plugged in for programming.
Übersicht der Parameter
No.
Topmost display
Middle display
1
26
button.
Undermost display
Meaning
(Selection,
* = default)
Operating mode of the digital input on the
interface module
*
Input inactive
Input used for high/low tariff switching of
meters
Input used for power interval
synchronization
Digital input
P
1
Hints
(input mode)
The time interval in the "Synctime" menu is
ignored
P