ADDITIONAL MOBILE HOME REQUIREMENTS
WARNING: DO NOT INSTALL IN SLEEPING
ROOM.
PARTS & MATERIALS REQUIRED (NOT SUPPLIED)
• A 80mm diameter chimney which complies to
UL 103, Standard for Factory-Built Chimneys for
Residential Type and Building Heating Appliances.
• Ceiling thimble suitable for use in mobile home.
• Roof thimble suitable for use in mobile home.
• Spark arrestor suitable for use in mobile home.
• Roof flashing suitable for use in mobile home.
ADDITIONAL INSTALLATION REQUIREMENTS
• The chimney shall attach directly to the room heater
and shall extend at least 3 feet (0.9 m) above the
part of the roof through which it passes.
• The top of the chimney is to be at least 2 feet (0.6
m) above the highest required elevation of any part
of the mobile home within 10 feet (3 m) of the
chimney.
• All roof-chimney terminations shall be able to be
readily removed at or below an elevation of 13½ feet
(4.1 m) above ground level and reinstalled without
the use of special tools or instructions.
• The chimney assembly shall be provided with
a mechanical securement means to secure the
chimney to the ceiling support box.
• Chimney Guard Requirements:
— When the chimney exits the mobile home at
a location other than through the roof, and
exits at a point 7 feet (2.1 m) or less above
the ground level on which the mobile home is
positioned, a guard or method of enclosing the
chimney shall be provided at the point of exit for
a height up to 7 feet.
— The chimney guard shall not have any openings
large enough that a 3/4 inch diameter rod can
enter.
— The chimney guard shall not have any openings
large enough that a 1/2 inch diameter rod can
enter beyond 4 inches
• The stove must be on installed on a level surface
which can support the weight of the stove.
• The stove must be bolted to the level surface so
that it permanently secured and can not be moved,
tipped, or have ventilation seals compromised.
• The stove must be provided a permanently ducted
source of outside air to support combustion which
meets the following requirements:
— The duct must be made of metal exclusively, not
other materials such as plastic.
Cleveland Iron Works Wood Pellet Fire Stove
— The end of this duct must be equipped with a
screen which prevents rodents from infiltrating.
— The end of this duct must be kept free of leaves,
snow, ice, or other debris that could restrict air
supply when the appliance is in operation.
• The joints of any and all connections for both of
ventilation systems (the inlet air and the combustion
exhaust) must be sealed with high temperature
silicone.
• The chimney must comply with all applicable
codes and requirements of the authority having
jurisdiction.
• The chimney must be removed for any mobile
home transportation, and reinstalled abiding all
requirements after transportation.
The flue system is based on negative pressure in
the combustion chamber and a slight overpressure
on the flue gas outlet. It is therefore important
that the flue gas connection is fitted correctly and
is airtight.
CAUTION: THE STRUCTURAL INTEGRITY OF
THE MOBILE HOME FLOOR, WALL, CEILING,
AND ROOF MUST BE MAINTAINED.
UL 103 Chimney
Joist Shield
/ Firestop
UL 103 Pass-through system
according to Manufacturer's Parts
& Instructions
Double-wall UL 103 High
Temperature Chimney Pipe
Floor
Protector
Figure 9 Mobile Home Vertical Chimney
10
Operating Instructions and Owner's Manual
Mandatory Chimney Cap &
Spark Arrestor
Storm Collar & Roof
Flashing per Local
Mobile Home Building
Codes
Mobile Home
Thimble
Chimney Support
Clean Out T
Permanent,
All-metal
Combustion air
Source with
Exterior Seal &
Screen
Bolted to floor