SMA Solar Technology America LLC
Rated grid volt-
Triggering
age
threshold - Trig-
gering voltages
240 V
50 %
88 %
110 %
120 %
Measuring precisions:
• Triggering threshold: ±2% of the rated grid voltage
• Tripping time: ±1% of the nominal tripping time
• Triggering frequency: ±0.2% of rated power frequency
10.4 General Data
Width x height x depth
Weight
Length x width x height of the packaging
Transport weight
Operating temperature range
Storage temperature
Maximum permissible value for relative humid-
ity, non-condensing
Maximum operating altitude above mean sea
level (MSL)
Typical noise emission
Self-consumption in standby mode without the
load necessary to supply the battery
Self-consumption without the load necessary to
supply the battery
Maximum data volume per inverter with Speed-
wire/Webconnect
Installation Manual
Triggering volt-
Triggering volt-
age - Neutral
age - L1 and L2
conductor
57.6 V to 62.4 V 115.2 V to
124.8 V
103.2 V to
206.4 V to
108.0 V
216.0 V
129.6 V to
259.2 V to
134.4 V
268.8 V
141.6 V to
283.2 V to
146.4 V
292.8 V
535 mm x 730 mm x 198 mm
(21.1 in x 28.7 in x 7.8 in)
800 mm x 600 mm x 300 mm
(31.5 in x 23.6 in x 11.8 in)
-25°C to +60°C (-13°F to +140°F)
-40°C to +60°C (-40°F to +140°F)
10 Technical Data
Tripping time
max. 0.1602 s
max. 2.002 s
max. 1.001 s
max. 0.1602 s
26 kg (57.32 lbs)
30 kg (66.14 lbs)
95 %
3000 m (9843 ft)
39 dB(A)
< 5 W
< 10 W
550 MB/month
SBSxx-US-10-IA-xx-11
67