31
OPERATING THE GENERATOR
Stopping the Engine
1. Turn OFF all electrical device switches
for connected loads.
2. Turn OFF the circuit breaker.
3. Allow the engine to run with no load for
about 5 minutes before stopping the
engine completely.
4. Turn the starter switch (key) to the "OFF"
position.
(1) Starter switch (key)
5. Turn the fuel filter cock to the "CLOSE"
position.
(1) Fuel filter cock
(2) Fuel filter pot
(A) "OFF"
(B) "ON"
(C) "PREHEAT"
(D) "START"
(A) "CLOSE"
If the Engine Fails to Stop in the Usual
Procedure (EMERGENCY STOP)
If the engine does not stop after turning the starter
switch (key) to "OFF" position, take the following
(EMERGENCY STOP) procedure.
WARNING
To avoid personal injury:
8 Keep your hands away from the
rotating parts, such as cooling
fan
and
personal injury may be caused
when manipulating the engine
stop lever.
1. Open the door, using the door knob.
2. Turn the engine stop lever to "STOP" direction and
hold it for 5 to 10 seconds to shut off the engine.
(1) Engine stop lever
3. After stopping the engine, make sure that the door
is closed and the starter switch (key) is at OFF.
4. The following causes are possible for such
unusual engine shut-off.
Pinpoint and correct the cause of trouble.
8 Check for the stop solenoid.
8 Check to see if the battery has discharged too
much or is in trouble.
8 Check
for
disconnection
terminals.
V-belt.
Otherwise
(A) "START"
(B) "STOP"
of
the
battery