Electrolock
When the function is enabled ( dip3= ON ), the output relay of the electrolock is activated for 450 mS at
any opening phase. The activation occurs even when the main switch is moved to position "0" and to "II" to
allow the motion of the door.
Adjusting
Trimmer T. Pause
Trimmer Closing speed
Trimmer Opening speed
Getting started
1 - Realize all the connections according to the diagram on pag. 25;
2 - Close the door;
3 - Power-up the system;
4 - Insert the battery protection fuse into its holder ;
5 - Verify the lighting of L1 and L2 : if there are no safety device connected connect a bridge between the
contacts 1-2 and 2-3;
6 - Set the external switch on the position I : "Automatic mode".
7 - If the operator hasn't been programmed yet the led LP flashes RED : skip to point 8.
Otherwise keep pushed P1 for 4 sec. until the led LP flashes GREEN, then release and push it again for a
while.The led LP will flash RED.
8 - Open manually the door : from this time on a self-adjusting cycle ( complete opening, pause and complete
closing), begins;
The led LP flashes RED all time long. At the end the door returns completely closed again and LP becomes
GREEN. The self-adjusting is over.
Main switch
I
0
II
The same features of the above main switch are available even on the terminals 4-5-6 of the electronic card,
allowing to connect a peripheral external switch.
Unplug the internal 3-wires connector if you want to disable the main switch and enable only the peripheral
switch.
ATTENTION: When you get an external command you need to put the switch in position 0 or I but never in II,
otherwise the door will stay always open!
Photostop: NC input for a safety photocell. When active stops the door . (Make a bridge if not used ). If
L1 is OFF the safety device is activated and the door is blocked.
Re-open photocell: NC input for a safety photocell. When active opens the door. ( Make a bridge if not
used ). If L2 is OFF the safety device is activated and the door is blocked.
External radar: NO input which opens the door. Connect to this function the external sensors which
has to be disabled in night mode ( acting upon the Day/Night selector ).
Internal radar: NO input which opens the door: it's always enabled.
Day/Night selector: NO input : when shorted to COMMON disables the night radar.
Start input : Input NO for external open button. When active opens or stops the door.
Pag. 28
: MAX 30 sec. - MIN immediate re-closing
: MAX 3 sec. [for an angle of 90°] - MIN 15 sec.
: MAX 3 sec. [for an angle of 90°] - MIN 15 sec.
Features description
Position I : Automatic mode .
Position 0 : Door open: the door opens and remains open as far as the
switch is in this position
Position II : Door free. The door is free and can be moved manually.
A CDV Group product