12. Test run

12.1. The following phenomena do not represent faults.

Phenomenon
Indoor unit does not perform cooling (heating)
operation.
The auto vane rotates and begins to blow air
horizontally.
Fan setting changes during heating.
Fan stops during heating operation.
Fan does not stop while operation has been
stopped.
No setting of fan while start SW has been
turned on.
Indoor unit remote controller shows "H0" or
"PLEASE WAIT" indicator for about five min-
utes when turning ON universal power sup-
ply.
Drain pump does not stop when unit is
stopped.
Drain pump continues to operate while unit
has been stopped.
Indoor unit emits noise when switching from
heating to cooling and vice versa.
Immediately after startup, the indoor unit
emits the sound of the refrigerant flow.
Warm air comes from an indoor unit that is
not performing a heating operation.

13. Information on rating plate

Model
Unit combination
Refrigerant (R410A)
Allowable pressure (Ps)
Net weight
Model
Unit combination
Refrigerant (R410A)
Allowable pressure (Ps)
Net weight
Model
Unit combination
Refrigerant (R410A)
Allowable pressure (Ps)
Net weight
Model
Unit combination
Refrigerant (R410A)
Allowable pressure (Ps)
Net weight
Model
Unit combination
Refrigerant (R410A)
Allowable pressure (Ps)
Net weight
Model
Unit combination
Refrigerant (R410A)
Allowable pressure (Ps)
Net weight
Model
Unit combination
Refrigerant (R410A)
Allowable pressure (Ps)
Net weight
Display of remote controller
"Cooling (heating)" flashes
Normal display
Normal display
Defrost display
No lighting
Heat ready
"H0" or "PLEASE WAIT" flashes
Light out
Normal display
Normal display
Normal display
P200
P250
-
-
6.5kg
9.0kg
185kg
200kg
P500
P250
P250
9.0kg
9.0kg
200kg
200kg
P650
P350
P300
11.5kg
9.0kg
245kg
215kg
P800
P450
P350
11.5kg
11.5kg
245kg
245kg
P950
P400
P300
11.5kg
9.0kg
245kg
215kg
P1050
P400
P350
11.5kg
11.5kg
245kg
245kg
P1150
P450
P350
11.5kg
11.5kg
245kg
245kg
When another indoor unit is performing the heating (cooling) operation, the cool-
ing (heating) operation is not performed.
If air has been blowing downward for 1 hour during cooling, the unit may
automatically change to horizontal blowing with the control operation of the auto
vane. During defrosting or immediately after heating start-up/shut-down, the auto
vane automatically rotates to blow air horizontally for a short period of time.
Ultra-low speed operation is commenced at thermostat OFF.
Light air automatically changes over to set value by time or piping temperature at
thermostat ON.
The fan is to stop during defrosting.
The fan is set to run for 1 minute after stopping to exhaust residual heat (only in
heating).
Ultra low-speed operation for 5 minutes after SW ON or until piping temperature
becomes 35°C, low speed operation for 2 minutes thereafter, and then set notch
is commenced (Hot adjust control).
The system is being started up.
Operate remote controller again after "H0" or "PLEASE WAIT" disappear.
After cooling operation stops, the unit continues to operate drain pump for three
minutes and then stops it.
Unit continues to operate drain pump if drainage is generated, even during a
stop.
This is a switching sound of the refrigerant circuit and does not imply a problem.
Unstable flow of the refrigerant emits a sound. This is temporary and does not
imply a problem.
The LEV is slightly open to prevent refrigerant, of the indoor unit that is not
performing the heating operation, from being liquefied. This does not imply a
problem.
P300
P350
-
-
9.0kg
11.5kg
HP: 4.15 MPa, LP: 2.21 MPa
215kg
245kg
P550
P300
P250
9.0kg
9.0kg
HP: 4.15 MPa, LP: 2.21 MPa
215kg
200kg
P700
P350
P350
11.5kg
11.5kg
HP: 4.15 MPa, LP: 2.21 MPa
245kg
245kg
P850
P450
P400
11.5kg
11.5kg
HP: 4.15 MPa, LP: 2.21 MPa
245kg
245kg
P250
P400
9.0kg
11.5kg
HP: 4.15 MPa, LP: 2.21 MPa
200kg
245kg
P300
P400
9.0kg
11.5kg
HP: 4.15 MPa, LP: 2.21 MPa
215kg
245kg
P350
P450
11.5kg
11.5kg
HP: 4.15 MPa, LP: 2.21 MPa
245kg
245kg
Cause
P400
P450
-
-
11.5kg
11.5kg
245kg
245kg
P600
P350
P250
11.5kg
9.0kg
245kg
200kg
P750
P400
P350
11.5kg
11.5kg
245kg
245kg
P900
P450
P450
11.5kg
11.5kg
245kg
245kg
P1000
P300
P300
9.0kg
9.0kg
215kg
215kg
P1100
P350
P350
11.5kg
11.5kg
245kg
245kg
P1200
P400
P350
11.5kg
11.5kg
245kg
245kg
21