The units of the output variables correspond to the units of the current values in the submenu
Basic setting / Units. These can be set in programme mode.
Example switching hysteresis (Hyst.)
11.3.7 Limit value 2 function
The limit value 2 function allows monitoring of whether a current value lies between two threshold
values. If the current value leaves or enters the range between the limit values, a signal can be is-
sued. The settable values largely correspond to those of the limit value function. Added to this is an
input for limit value 2:
Output 4
...
Funct.
Limit value 2
...
Limit2
100.0 °C
...
11.3.8 Function 0 – 20 mA
With the 0 – 20 mA function, an analogue signal is issued. With this function, the signal receiver can-
not detect a power cut
Output 7
...
Funct. 0 – 20 mA
Outvar: temp. cold
Status 10.000 mA
0/4 mA
0.0°C
20mA
200.0 °C
I-ErrU
21.5 mA
....
26
Limit value Th 80.0 °C, switching hysteresis 2 %:
Make point = 80.0
Break point = (1 – 0.02) * 80°C = 78.4 °C
Remark
Select the output with the
Output function twofold limit value
Limit value 2
Setting 0.1 to 999999
For setting of the units see Limit value function
Remark
Select the output with the
Analogue output 0 – 20 mA
Settable
Select the output variables (current values)
Value that is transmitted from the processor to the output.
Current value
In case of a module fault, the real value may deviate.
Min. value,
Value of the output variable which corresponds to 0 mA
settable
Max. value,
Value of the output value which corresponds to 20 mA
settable
Current output
Possible settings:
in case of
- Continuous current: Signal unchanged in case of error
error
- 21.5 mA:
- 0 / 3.5 mA:
keys
keys
In case of error 21.5 mA
In case of error 0 mA / 3.5 mA
®
CALEC
energy master, Output 24V