G
B
trimmer and LED DL6 on).
POWER SENSOR ALARM
The T2 24V control panel has automatic sensors that make the movement of the gate
reverse in case of impact against objects or persons in accordance with the current EN
standards (always use the right tool to ensure compliance with the values imposed by the
standard), without special adjustments on the control panel, as it operates using special
internal software.
If the power sensor is used in opening or closing (only in high-speed) and then again, in
the opposite direction, the gate stops and then reverses for 1 second.
The alarm status will be displayed by the blinker which will remain active for one minute,
during which time you can restore gate operation by pressing any command button.
FUNCTIONING IN DEAD MAN MODE WHEN THE SAFETY DEVICES ARE FAILING
If the safety edge fails or remains engaged for more than 5 seconds, or if photocell fails
or remain engaded for more than 60 seconds, the open, close, k button and pedestrian
commands will work only in dead man mode.
The signal that this mode has been activated is given by the blinking of the programming
led.
With the blinking of the programming led, the opening and closing operation are allowed
only with the command button pressed and held. The radio commands and that of
automatic closing, will be excluded, since their use in this mode, is not allowed by the
norms.
Once the failing safety device is repaired, in automatic after 1 second, all standard
commands that were selected, such as step by step, automatic mode, radio commands
and automatic closing start functioning again.
Note 1: during this functioning in dead man mode, in case of damage to the safety
strips (or photocells) the photocells (or safety strips) still work by interrupting the
operation in progress.
Note 2: the stop command is not to be considered a safety command that can be
bypassed in this mode. Therefore, when pressed or damaged, it will not allow
any movement of the gate.
The dead-man operation is only an emergency operation which must be activated
for a very short period and with the complete installation at sight so to have a
secure and safe control of the system. As soon as possible however, the failing
safety devices must be repaired and activated.
BLINKER
N.B.: This control panel can power ONLY BLINKERS ON A (ACG7061) CIRCUIT with lamps
up to 24V and 20W.
PRE-BLINKING
DIP 5 - OFF => the motor and blinker begin simultaneously.
DIP 5 - ON => the blinker begins 3 seconds before the motor.
GATE OPEN WARNING LIGHT (COM-SIGNAL)
Signals when the gate is open, partially open or not closed completely. Turns off only
when the gate is completely closed.
This signal is active during programming.
N.B.: Max 3 W. If push buttons or lamps are in excess, the control panel processes will
be endangered and possibly halt operation.
OPERATION AFTER A BLACK-OUT (WITHOUT BATTERIES)
When the power supply comes back the DL1 led turns on and remains on for all the time
the gate stays open. The led will turn off only once the gate is completely closed.
It is recommended to fully open the gate. Let the gate close by itself or with automatic
closing, or wait until the blinker stops flashing before commanding it to close.
This will allow the gate to realign. If, motors were released and moved from the normal
position when closed during the blackout, the first movement after power returns must
be complete.
If the black out occurs when the gate is still moving or when the gate is open and the
first command sent after the black out is a closing command, the closing of the gate will
be carried out with a total delay between the two gate leaves. Therefore, first the leaf M2
will close completely; once it is off, M1 will start closing. This separate movement of the
two gate leaves is done to avoid their incorrect overlapping.
TECHNICAL SPECIFICATIONS
- Temperature range
- Humidity
- Voltage
- Frequency
- Battery power
- Transformer Power
- Maximum absorption
- Network Micro-switches
- Maximum power gate open indicator
- Maximum blinker power
- Power available for photocells and accessories
- Power available for radio connector
RADIO SPECIFICATIONS (model T2 24V CRX)
- Receiving Frequency
- Impedance
- Sensitivity
- Pick-up time
- Drop time
- All inputs must be used as clean contacts because the power is generated internally
(secure power) to the board and is set up to ensure compliance with double or
reinforced insulation with regard to dangerous voltage.
- Any external circuits connected to the outputs of the control panel must be made in
such a manner as to ensure compliance with double or reinforced insulation with regard
to dangerous voltage.
- All inputs are controlled by a programmed integrated circuit that performs a self check
every time it starts operating.
28
0 ÷ 55°C
<95% without condensation
230V~ ± 10%
(120V/60Hz upon request)
50/60 Hz
20-24Vdc
130VA -
primary 230Vac
secondary 18Vac
50 mA
100ms
24Vdc 3W (equivalent to one 3W
or 5 LED light bulb with resistor in
series at 2.2 K ohm)
24Vdc 20W
1A ± 15%
200Ma
433,92 MHz
52 OHM
>2,24µV
300ms
300ms