At the same time LED DL1 stops flashing indicating exit from programming. Safety
and other gate commands now operate normally (inversions, stop, alarms, etc.).
Upon closing the power sensor stops the gate.
4 - AFTER PROGRAMMING RESET DIP 2 TO OFF.
(#) DURING PROGRAMMING THE SAFETY DEVICES ARE ACTIVE AND STOP THE
PROGRAMMING PROCEDURE (LED DL1 FROM FLASHING BECOMES CONSTANT).
TO REPEAT PROGRAMMING SET DIP 2 TO OFF, CLOSE THE GATE USING THE
PROCEDURE "MOTOR ROTATIONAL DIRECTION CONTROL" AND REPEAT THE
DESIRED PROGRAMMING PROCEDURE.
D - SETTING THE TIME FOR 2 MOTORS (#) WITH TIME OPERATION
(DIP 7 OFF)
1 - The gate must be completely closed.
2 - Set DIP 2 to ON => LED DL1 will blink rapidly.
3 - Press the PROG button. => M1 opens.
4 - When the mechanical opening stop is reached, wait a second then press the PROG
button => M1 stops and M2 opens.
5 - When the mechanical opening stop is reached => wait 1 second and press the PROG
button => M2 stops.
6 - Press the PROG button => M2 closes.
7 - Press the PROG button => M1 closes setting the time lag between M2 and M1.
At the same time LED DL1 stops flashing indicating exit from the programming
procedure.
Safety and other gate commands now operate normally (inversions, stop, alarms,
etc.).
8 - After the set amount of time, the gate will stop.
9 - AT THE END OF PROGRAMMING RESET DIP 2 TO OFF.
NOTE: The slowdown is automatically determined by the control board during the time
setting phase and is activated at about 50 to 60 cm before reaching the mechanical
opening or closing limit.
D - SETTING THE TIME FOR 1 MOTOR (#) WITH TIME OPERATION
(DIP 7 OFF)
CAUTION: FOR ONE MOTOR CONTROL DIP 13 MUST SET TO ON
1 - The gate must be completely closed.
2 - Set micro-switch DIP 2 to ON => LED DL1 will blink rapidly.
3 - Press the PROG button => M1 opens.
4 - When the mechanical opening stop is reached, wait a second then press the PROG
button => M1 stops.
5 - Press the PROG button => M1 closes.
At the same time LED DL1 stops flashing indicating exit from the programming
procedure.
Safety and other gate commands now operate normally (inversions, stop, alarms,
etc.).
6 - After the set amount of time, the gate will stop.
7 - AT THE END OF PROGRAMMING RESET DIP 2 TO OFF.
D - SETTING PEDESTRIAN OPENING TIMES (#) BOTH FOR TIME AND
POWER SENSOR OPERATION
With gate closed:
1 - First set DIP2 to ON (LED DL1 flashes quickly) and then DIP1 to ON ( LED DL1 flashes
slowly).
2 - Push the pedestrian button (COM-PED.BUTT) => M1 opens.
3 - Push the pedestrian button to stop movement (thereby setting M1 opening).
4 - Push the pedestrian button to start closing.
5 - Upon closing reset DIP 1 and 2 to OFF.
(#) DURING PROGRAMMING THE SAFETY DEVICES ARE ACTIVE AND STOP THE
PROGRAMMING PROCEDURE (LED DL1 FROM FLASHING BECOMES CONSTANT).
TO REPEAT PROGRAMMING SET DIP 2 TO OFF, CLOSE THE GATE USING THE
PROCEDURE "MOTOR ROTATIONAL DIRECTION CONTROL" AND REPEAT THE
DESIRED PROGRAMMING PROCEDURE.
E - RADIO CODE PROGRAMMING FOR TOTAL OPENING
(UP TO 62 CODES - CRX MODELS ONLY)
Programming can be done only when the gate is stationary.
1 - First set DIP 1 to ON and then DIP 2 to ON.
2 - The red LED DL1 flashes ON every 1 sec. and OFF for 10 seconds.
3 - Press the remote control button (usually channel A) within the allotted 10 seconds. If
the remote is memorized properly LED DL10 (green) blinks.
4 - The programming time for codes is automatically renewed in order to memorize the
next remote control.
5 - To finish programming, wait 10 seconds, or press the PROG button briefly. The red
LED DL1 stops flashing.
6 - Reset DIP 1 to OFF and DIP 2 to OFF.
7 - End of procedure.
CANCELLATION OF ALL RADIO CODES FOR TOTAL OPENING
Cancellations can only be performed when gate is stationary.
1 - Set DIP 1 to ON and then DIP 2 to ON.
2 - The red LED DL1 flashes ON every 1 second and OFF for 10 seconds.
3 - Press and hold the PROG button for 5 seconds. Memory cancellation is indicated by
two flashes of green LED DL10.
4 - The red LED DL1 remains active and you can add new codes as shown above.
5 - Reset DIP 1 to OFF and DIP 2 to OFF.
6 - End of procedure.
INDICATOR MEMORY FULL OF RADIO CODES FOR TOTAL OPENING
Indication only when gate is stationary.
1 - Set DIP 1 to ON and then DIP 2 to ON.
2 - The green LED DL10 flashes 6 times when the memory is full (62 codes).
3 - LED DL1 will then remain active for 10 seconds enabling possible cancellation of
codes.
4 - Reset DIP 1 to OFF and DIP 2 to OFF.
5 - End of procedure.
F - PROGRAMMING PEDESTRIAN OPENING RADIO CODES
(UP TO 62 CODES - CRX MODELS ONLY)
Programming can be done only when the gate is stationary.
1 - Set DIP 1 to ON and then DIP 3 to ON.
2 - The red led DL1 flashes ON for 1 second and OFF for 1 second for 10 seconds.
3 - Press the remote control button (usually channel B) within the allotted 10 seconds. If
the remote is properly memorized LED DL10 (green) blinks.
4 - The programming time for codes is automatically renewed in order to memorize the
next remote control.
5 - To finish programming wait 10 seconds, or press the PROG button briefly. The red
LED DL1 stops flashing.
6 - Reset DIP 1 to OFF and DIP 3 to OFF.
NOTE: If LED DL1 CONTINUES BLINKING QUICKLY IT MEANS THAT DIP 1 IS STILL
SET TO ON AND THAT ANY OPERATION IS REFUSED.
7 - End of procedure.
CANCELLATION PROCEDURE FOR ALL PEDESTRIAN OPENING RADIO CODES
Cancellation can only be performed when the gate is stationary.
1 - Set DIP 1 to ON and then DIP 3 to ON.
2 - The red LED DL1 flashes ON for 1 second and OFF for 1 second for 10 seconds.
3 - Press and hold the PROG button for 5 seconds. Memory cancellation is indicated by
two flashes of green LED DL10.
4 - The red LED DL1 remains active and you can add new codes as shown above.
5 - Reset DIP 1 to OFF and DIP 3 to OFF.
6 - End of procedure.
INDICATION MEMORY FULL OF PEDESTRIAN OPENING RADIO CODES
Indication only when the gate is stationary.
1 - Set DIP 1 to ON and then DIP 3 to ON.
2 - The green LED DL10 flashes 6 times when the memory is full (62 codes).
3 - The LED DL1 will then remain active for 10 seconds enabling possible cancellation
of codes.
4 - Set DIP 1 to OFF and DIP 3 to OFF.
5 - End of procedure.
26