Fig. 1: Charge voltage vs. temperature for solar mode. Charge modes:
1)
With switch regulator (two-step controller): Charge on curve B (max. charge voltage)
for max. 2 hrs per day, then switch over to continuous charge – Curve C
2)
Standard charge (without switching) – Curve A
3)
Boost charge (Equalizing charge with external generator): Charge on curve B for max.
5 hrs per month, then switch over to curve C.
2.5 Alternating currents
When recharging acc. to fig.1 the actual value of
the alternating current is occasionally permitted
to reach 10 A (RMS)/ 100 Ah C
fully charged state during float charge the actual
value of the alternating current must not exceed
5 A (RMS)/ 100 Ah C
-capacity.
10
2.6 Charging currents
The charging current should range between 10 A
to 35 A / 100Ah C
-capacity (guide values).
10
35 A/100 Ah C
-capacity must not be exceeded
10
in cyclical operation.
2.7 Temperature
The recommended operation temperature range
for lead acid batteries is 10° C to 30° C (best 20° C
± 5 K). Higher temperatures will seriously reduce
service life. Lower temperatures reduce the avai-
lable capacity. The absolute maximum tempera-
ture is 55° C and should not exceed 45° C in ser-
vice.
2.8 Temperature-related charge voltage
The temperature related adjustment has to be
carried out acc. to fig. 1. An adjustment of the
charge voltage must not be applied within a tem-
perature range 15° C to 35° C.
2.9 Electrolyte
The electrolyte is diluted sulphuric acid and fixed
in a gel.
3. Battery maintenance and control
Keep the battery clean and dry to avoid leakage
currents. Plastic parts of the battery, especially
containers, must be cleaned with pure water
without additives.
At least every 6 months measure and record:
Battery voltage
Voltage of several blocks/cells during
discharge
Surface temperature of several blocks/cells
Battery-room temperature
en
6
If during the discharge the voltage of one or
more cells/blocks differs from the average
discharge voltage more than shown in the follo-
-capacity. In a
wing table or if the surface temperature differen-
10
ce between cells/blocks exceeds 5K an equali-
zing charge acc. To item 2.4 shall be carried out.
In addition, annual measurements and recor-
ding:
Battery voltage
Voltage of all blocks/cells during discharge
Surface temperature of all blocks/cells
Battery-room temperature
Type
2 V cells
6 V blocks
12 V-blocks
Annual visual checks:
Screw connections
Screw connections without locking device
have to be checked for tightness.
Battery installation and arrangement
Ventilation
4. Tests
Tests have to be carried out according to
IEC 60896-21.
Capacity test, for instance, acceptance test
on site: In order to make sure the battery is fully
charged the following IU-charge methods must
be applied: Option 1: float charge (see item 2.3),
≥ 72 hours. Option 2: 2.40 Vpc, ≥ 16 hours (max.
48 hours) followed by float charge (see item 2.3),
≥ 8 hours. The current available to the battery
must be between 10 A/100 Ah and 35 A/100 Ah
of the C
-capacity.
10
5. Faults
Call the service agents immediately if faults in
the battery or the charging unit are found.
Recorded data as described in item 3. must be
made available to the service agent. It is recom-
mended that a service contract is taken out with
your agent.
6. Storage and taking out of operation
Refreshening charge shall be carried out latest if
the open circuit voltage is decreased to the fol-
lowing guide values: 2.115 Vpc respectively
6.345 V (6V-block), 12.69 V (12V-block).
To store or decommission cells/blocks for a
longer Period of
charged and stored in a dry and cold but frost-
free room, away from direct sun light. To avoid
damage the following charging methods can be
chosen:
1. Maximum storage time is 17 months at
≤ 20° C. Equalizing charges will be required
at higher temperatures, for instance, after
8.5 months at 30° C.
2. Float charging as detailed in 2.3.
7. Transport
Cells/block batteries must be transported in an
upright position. Batteries without any visible
damage are not defined as dangerous goods
under the regulations for transport of dangerous
goods by road (ADR) or by railway (RID). They
must be protected against short circuits, slip-
ping, upsetting or damaging. Cells/block batteries
may be suitable stacked and secured on pallets
(ADR and RID, special provision 598). It is prohi-
bited to staple pallets.
No dangerous traces of acid shall be found on
the exteriors of the packing unit.
Cells/block batteries whose containers leak or
are damaged must be packed and transported
as class 8 dangerous goods under UN no. 2794.
In case of air transport, batteries which are part
of any equipment must be disconnected at their
terminals, and the terminals must be protected
against short-circuits. This is in order to avoid
the risk of any incidents like fire etc.
deviation
-0.2 V
-0.35 V
-0.49 V
time they should be fully