Con1
Con2
Structure of configuration word 1 ( Con1):
 1
Relay
0 Signaller direct
1 Signaller inverse
2 2-pnt.contr. direct
3 2-p.contr. inverse
4
2-p. positioner
5
3-pnt.contr. *
6
3-p. positioner *
Ü Output is not used.
* Code is not adjustable for versions with 2 relays.
# The limit contact is suppressed during start-up or after set-point
changes.
< For description of heating current monitoring Ä right page.
>
: normally open contact, relay 3 energized with alarm.
: normally closed contact, relay 3 de-energized with alarm. +
y Without decimal point (parameter dP = 0) the range is -99...500 °C.
x With 3-pnt.controllers: with FbF and PoL heating and cooling = OFF.
I
Con2
 2
Logic Relay
Ü
Ü
Ü
Ü
Ü
Display
0
°C
1
°C
2
°F
3
°F
D
Measurement loop
monitoring x
Unit reacts as x >> w
Unit reacts as x << w
Unit reacts as x >> w
Unit reacts as x << w
Con1
M
 3 (alarm relay)
Limit
Heating Principle
contact curr. <
0 relative
-
1 absolute
-
2 relative
f
3 absolute
f
4 relative
-
5 absolute
-
6 relative
f
7 absolute
f
8 rel. #
-
9 rel. #
-
Input type
0 type L
1 type J
2 type K
3 type N
4 Type S
5 Type R
6 Pt 100 - 99,9...500,0 °C
- 99,9...500,0 °C y
7 0...20 mA linear
8 4...20 mA linear
9 0...10 V linear
>
n.c.
n.c.
n.c.
n.c.
n.o.
n.o.
n.o.
n.o.
n.o.
n.o.
0...900 °C
0...900 °C
0...900 °C
0...900 °C
0...1350 °C
0...1350 °C
0...1300 °C
0...1300 °C
0...1760 °C
0...1760 °C
0...1760 °C
0...1760 °C