1. General information

1.1.
Information regarding installation and
operating instructions
These installation and operating instructions
help the tradesman to install, put into opera-
tion and service the "Regufloor HX".
Before installation, the installation and operat-
ing instructions are to be read in their entirety!

1.2. Symbol explanation

Guidelines for the safety of persons and the
installation itself are displayed by symbols.
These guidelines must be observed in order
to avoid accidents, damage to property and
malfunctions.
DANGER!
Imminent danger to life and limb!
ATTENTION!
Possible danger to product, installation or
environment!
NOTE!
Useful information and notes.

1.3. Copyright

The installation and operating instructions as
well as the included texts, drawings, images
and other illustrations are copyrighted.

2. Safety notes

The "Regufloor HX" has to be installed by an
authorised specialist tradesman with due con-
sideration of the valid standards and rules. We
do not accept liability for damages and mal-
functions caused by nonobservance of these
instructions.
WARNING! Risk of scalding!
Hot escaping fluids may lead to bad
scalds. Hot pipes may also lead to scalds!
3.

Technical data

3.1. Dimensions

See illustr. 3.1.
Minimum depth of 160 mm required inside the
cabinet.
Installation and operating instructions

3.2. Performance data

Max. working pressure
Primary side:
Secondary side:
Diaphragm safety valve:
Max. flow temperature
Primary side:
Secondary side:
Control range:
Volume diaphragm
expansion tank:
Heat exchanger:
Pump:
System volume:
Max. system volume related to the expansion
tank (volume 3 l) depending on the flow tem-
perature.
Conversion of the max. system volume to the
possible total pipe length related to the pipe
dimension.
The water seal of the expansion tank
amounts to 0.6 l (corresponds to 20% of the
tank volume (3 l), according to DIN 12828
appendix D.2).
Flow
temperature V
max
30°C
220 l
35°C
150 l
40°C
115 l
45°C
90 l
50°C
80 l
55°C
60 l
403
Illustr. 3.1: Dimensions "Regufloor HX"
"Regufloor HX"
6 bar
3 bar
3 bar
90°C
50°C
20° - 50°C
3 l
14 plates
Wilo
17 x 2
16 x 2
14 x 2
1655 m
1945 m
2800 m
1130 m
1325 m
1905 m
865 m
1015 m
1460 m
675 m
795 m
1145 m
600 m
705 m
1015 m
450 m
530 m
760 m