12. Enter the desired deviation alarm tolerance. The deviation alarm is an alarm point that
changes with the temperature set point. If this alarm point is exceeded, the alarm horn
sounds and ALARM displays in the zone operating screen.
13. Enter the desired shutdown alarm tolerance. The shutdown alarm is an alarm point that
changes with the temperature set point. If this alarm point is exceeded, the alarm horn
sounds and the controller aborts the cure cycle. A notification of the cycle abort displays in
the zone screen.
14. Enter the vacuum high and low alarm set points. The alarm sounds and ALARM displays in
the zone operating screen if either of these points are exceeded. Exceeding either of the
vacuum alarm points does not cause the controller to abort the cure cycle.
15. Set Zone 2 Slave Mode to ON or OFF (dual zone units only). Setting the slave mode to ON
assigns all 20 thermocouples to Zone 1.
16. Specify active and inactive thermocouples. Active thermocouples are indicated by a check
mark in the check box next the corresponding thermocouple number. Touch the check boxes
to remove the check mark from the inactive thermocouples.
17. Press the CONTINUE TO STEP 3 button.!
®
© BriskHeat
Corporation. All rights reserved.
®
ACR
3 Hot Bonder
17
18. Fill in all fields to the desired setting. Touch FINISH when complete:

Ramp Rate: the heat up rate in degrees per minute from starting temperature to
Dwell Temperature.

Dwell Temp: the temperature the program is to hold for the programmed length of
time.

Dwell Time: the length of time to hold at the programmed Dwell Temperature.

Cool Down Rate: the rate in degrees per minute from the last dwell temperature to
the End of Cycle Temp.
NOTE: Since the Hot Bonder cannot force an object to cool down faster than the
physical conditions will allow, both high temperature alarms are disabled during
the cool down phase.

End of Cycle Temp: the temperature at which the cure is considered complete.
NOTE: The end of cycle temperature must be above the ambient temperature for it to
complete.
®
© BriskHeat
Corporation. All rights reserved.
®
ACR
3 Hot Bonder
18