2.1

DIMENSIONS

SAFETY BARRIER
*REQUIRED DIMENSION WITH THE OPTIONAL BLOWER KIT INSTALLED.
2.2

MINIMUM CLEARANCE TO COMBUSTIBLES

This appliance must be recessed into a vented non-combustible wood-burning appliance (prefabricated or
masonry) only. The minimum appliance opening size in which the appliance is to be installed is:
HEIGHT 21
1
/
" (54.6cm)
2
The minimum allowable chimney fl ue size is 7" (178mm) round.
*Add 4" (102mm) for optional blower.
The minimum distance, from the bottom of a combustible mantel projecting 3" (76mm) maximum from the
wall to the top of the appliance, is 14" (35.6cm) (see "MINIMUM MANTEL CLEARANCES" section).
2.3

GENERAL INSTRUCTIONS

ALWAYS LIGHT THE PILOT WHETHER FOR THE FIRST TIME OR IF THE GAS SUPPLY HAS RUN OUT,
PROVIDE ADEQUATE CLEARANCE FOR SERVICING AND OPERATING THE APPLIANCE.
OBJECTS PLACED IN FRONT OF THE APPLIANCE MUST BE KEPT A MINIMUM OF 48 INCHES
SURFACES AROUND AND ESPECIALLY ABOVE THE APPLIANCE CAN BECOME HOT. AVOID CONTACT
HIGH PRESSURE WILL DAMAGE VALVE. DISCONNECT GAS SUPPLY PIPING BEFORE PRESSURE TESTING GAS
LINE AT TEST PRESSURES ABOVE 1/2 PSIG. CLOSE THE MANUAL SHUT-OFF VALVE BEFORE PRESSURE
TESTING GAS LINE AT TEST PRESSURES EQUAL TO OR LESS THAN 1/2 PSIG (35mb).
USE ONLY WOLF STEEL APPROVED OPTIONAL ACCESSORIES AND REPLACEMENT PARTS WITH THIS APPLIANCE.
USING NON-LISTED ACCESSORIES (BLOWERS, DOORS, LOUVRES, TRIMS, GAS COMPONENTS, VENTING
COMPONENTS, ETC.) COULD RESULT IN A SAFETY HAZARD AND WILL VOID THE WARRANTY AND CERTIFICATION.
THE APPLIANCE MUST NOT BE OPERATED AT TEMPERATURES BELOW FREEZING (32°F / 0°C).
THIS GAS APPLIANCE SHOULD BE INSTALLED AND SERVICED BY A QUALIFIED INSTALLER to
conform with local codes. Installation practices vary from region to region and it is important to know the
specifi cs that apply to your area, for example in Massachusetts State:
This product must be installed by a licensed plumber or gas fi tter when installed within the
commonwealth of Massachusetts.
The appliance damper must be removed or welded in the open position prior to installation of an
appliance insert or gas log.
The appliance off valve must be a "T" handle gas cock.
The fl exible connector must not be longer than 3 feet (0.9m).
A Carbon Monoxide detector is required in all rooms containing gas fi red appliances.
The appliance is not approved for installation in a bedroom or bathroom unless the unit is a direct vent
sealed combustion product.
21"
533mm
20 1/2"
9 1/2"
521mm
241mm
WIDTH 29" (73.7cm)
WITH THE GLASS DOOR OPENED OR REMOVED.
PROVIDE ADEQUATE VENTILATION.
NEVER OBSTRUCT THE FRONT OPENING OF THE APPLIANCE.
(121.9cm) FROM THE FRONT FACE OF THE APPLIANCE.
WHEN THE APPLIANCE IS OPERATING.
FIRE RISK. EXPLOSION HAZARD.
ALLOW THE APPLIANCE TO WARM TO ABOVE FREEZING PRIOR TO OPERATION.
17 1/2"
445mm
12"
305mm
17 1/2"
*
445mm
DEPTH *13
1
/
" (34.9cm)
4
WARNING
!
5
22 7/8"
581mm
13 1/4"
337mm
29 5/8"
753mm
W415-1355 / A / 11.16.16