PRODUCT DESCRIPTION
This submersible pump is for use in basins or lift stations and is suitable for pumping clear water and other
non-explosive, non-corrosive liquids. Do not use the pump in applications where sewage or any other debris
(gravel, sand, floating debris, etc.), abrasives, or corrosives are present.
These products have been carefully tested, inspected, and packaged to ensure safe delivery and operation.
Please examine your pump carefully to ensure that no damage occurred during shipment. If damage has
occurred, please contact the place of purchase. They will assist you in replacement or repair, if required.
The pump motor is equipped with an automatic resetting thermal protector, and may restart unexpectedly.
Thermal Protector tripping is an indication of motor overloading or overheating, which can be caused by
application issues such as an obstructed pump impeller, float stuck in the ON position, pump running dry,
pump air-locked, pump short cycling, excessively high or low voltage supply, or possibly a pump, motor,
bearings, or seal that have reached the end of their useful life.
This product is covered by a Limited Warranty for a period of 36 months from the date of original purchase
by the consumer. For complete warranty information, refer to www.redlionproducts.com; or call Technical
Support for a printed copy.
Models
Model
HP
RL-SC33T
1/3
RL-SC33V
1/3
RL-SC50T
1/2
RL-SC50V
1/2
Flow Rates
At Height: (Head)
RL-SC33T
RL-SC33V
RL-SC50T
RL-SC50V
Specifications
Discharge Size
1-1/2" FNPT
Intake Size
3/8" (9.5 mm) screened opening
Pump Housing
Cast iron (including volute and screen)
Impeller
Vortex design
Motor
Single phase PSC with automatic reset thermal overload protection
Hardware
300 series stainless steel
Bearings
Ball bearings
Pump Shaft Seal
Mechanical, spring-loaded, stationary carbon with Nitrile boot and rotating ceramic seat
The motor housing contains oil to cool the motor and to lubricate the bearings and seals. These pumps can
be operated with the motor housing partially exposed for extended periods of time. However, for the best
Cooling
cooling and longest motor life, the liquid level being pumped should normally be above the top of the
pump housing.
Amps Voltage Float Type
4.3
115
Tethered
4.3
115
Vertical
5.3
115
Tethered
5.3
115
Vertical
Gallons/Liters per Hour
5 ft (1.5 m)
10 ft (3 m)
3000 / 11356
2460 / 9312
3000 / 11356
2460 / 9312
3840 / 14536
3000 / 11356
3840 / 14536
3000 / 11356
On/Off Levels
13" (330 mm)/5" (127 mm)
7" (178 mm)/2.25" (57 mm)
13" (330 mm)/5" (127 mm)
7" (178 mm)/2.25" (57 mm)
15 ft (4.5 m)
20 ft (6.1 m)
1860 / 7041
1860 / 7041
2220 / 8404
2220 / 8404
PRODUCT DESCRIPTION
Minimum Basin Diameter
18" (457 mm)
15" (381 mm)
18" (457 mm)
15" (381 mm)
Shut Off
960 / 3634
25 ft (7.6 m)
960 / 3634
25 ft (7.6 m)
1440 / 5451
28 ft (8.5 m)
1440 / 5451
28 ft (8.5 m)
Models