FSFTM - CO
ATTENTION! 
The minimum CO
concentration of outdoor air amounts to approx. 350 ppm (output voltage = 1.75 V at MR = 0...2000 ppm or 0.7 V at
2
MR = 0...5000 ppm) in leafy, hardly industrialised areas. Gas inter-exchange in the sensor element happens by diffusion. Depending on the changes
to the concentration and the flow velocity of the air surrounding the sensor, the reaction of the device to the change of concentration may take
place with a delay. It is essential to choose an installation location for the device in which the air stream flows around the sensor. Otherwise the
gas exchange may be considerably delayed or prevented.
Automatic calibration of the carbon dioxide measurement – (default)
The automatic background logic is a self-calibrating mechanism that is suitable for use in applications in which the CO
air level (350 - 400 ppm) at least three times in 7 days. This should typically occur during times in which rooms are unoccupied. The sensor reaches
its normal accuracy after 24 hours of continuous operation in an environment that has been subjected to a fresh air supply of 400 ppm CO
deviation errors remain minimal if the sensor is exposed to fresh air at least 4 times within 21 days. The device needs continuous operating cycles
of more than 24 hours to operate correctly.
Manual calibration of carbon dioxide measurement
Manual calibration can be carried out independently of the DIP switch position.
Sufficient fresh air (CO
content = 500 ppm) must be provided before and after the calibration procedure!
2
The calibration procedure is started by pressing the "Reset CO
This is signalled by the flashing LED.
Then calibration takes place.
During this phase, the LED is constantly active.
The LED is deactivated after successful calibration.
®
AERASGARD
FSTFM - CO
Type ⁄ WG02
Measuring Range
CO
FSTFM - CO
- Modbus
2
FSFTM-CO2-MODBUS
0...5000 ppm
FSFTM-CO2-MODBUS P
0...5000 ppm
Data points:
relative humidity [% r. H.], temperature [°C], CO
and setpoint potentiometer

ACCESSORIES

KA2 -Modbus
Communication adapter (with USB and RS485 interface)
for system connection (incl. quick-start software)
LA -Modbus
Line termination device (with terminating resistor)
as an active bus termination of RS485 networks
- Modbus
2
- Modbus Room temperature humidity and CO
2
Humidity
2
0...100 % r. H.
0...100 % r. H.
" (for approx. five seconds).
2
Control
Temperature
element
0...+50 °C
0...+50 °C
Potentiometer
content of the air [ppm]
2
11
concentration drops to fresh
2
sensor, in-wall
2
Output
Item No.
Modbus
1501- 9226-6001- 162
Modbus
1501- 9226-6501- 282
1906- 1200- 0000- 100
1906- 1300- 0000- 100
Rev. 2020 - V12