Standard Type
LG 5944.02PC/61
Article number:
• Output:
• Nominal voltage U
:
N
• Width:
Ordering Example
LG 5944 .02 _ _ /_ _ _ /61 AC/DC 24 V
Troubleshooting
Failure
LED "Power" does not light up
LED "K1" lights up,
but "K2" remains off
LED "K2" lights up,
but "K1" remains off
Device cannot be activated
Maintenance and repairs
- The device contains no parts that require maintenance.
- In case of failure, do not open the device but send it to manufacturer
for repair.
AC/DC 24 V
0059038
2 NO contacts
AC/DC 24 V
22.5 mm
Nominal voltage
UL-approval
Termination resistor of the
safety edge in
2 wire connection
0 ... 1.2 kΩ
1 ... 8.2 kΩ
Number of safety edges
wire connection
0 device for 1 safety edge
(2- and 4- wire connection
possible)
1 device for 2 safety edges
(only 2-wire connection
possible)
Type of terminals
without indication:
terminal blocks fixed
with screw terminals
PC (plug in cage clamp):
pluggable terminal blocks
with cage clamp terminals
PS (plug in screw):
pluggable terminal blocks
with screw terminals
Contacts
Type
Potential cause
- Power supply not connected
- Cross fault between S11 and S21
- Safety relay K1 is welded
(replace device)
- A 1-channel switch-off occurred on
S12 (switch channel off on S22)
- Safety relay K2 is welded
(replace device)
- A 1-channel switch-off occurred on
S22 (switch channel off on S12)
Manual start mode:
- Line fault on start-button (disconnect
power supply and remove fault)
Automatic start mode:
- S33-S34 not bridged
- A safety relay is welded (replace device)
- Incorrect setting of switch S1
Characteristics
250
200
150
100
50
0
0,1
0,3 0,5
1
switching current A
safe breaking, no continuous arcing,
max. 1 switching cycle / s
Arc limit curve
15
3
5
10