2.6

Technical specifications

2.6.1

General

Designation

Dimensions

Weight (without packaging)
Rated voltage MCM10
Frequency
Max. on-site fuse protection of the
input voltage
Power draw MCM10
Rated voltage BUS
Internal appliance fuse, heating
pump output
Measuring range, supply
temperature sensor
Measuring range, outside
temperature sensor
Permissible ambient
temperature MCM10
Permissible ambient temperature,
supply temperature sensor
Permissible ambient temperature
outdoor temperature sensor
Maximum cable length,
2-wire BUS connections
Maximum lead lengths,
sensor leads
EMC suppression level to
Enclosure rating
NEMA definition
Tab. 1 General
2.6.2
Dimensions
2-1/2" (62mm)
2-1/2" (62mm)
9-1/4" (235mm)
6 720 616 690-03.1TD
Fig. 2
Dimensions
MCM10
Unit
(
Fig. 2)
lb (kg)
1.76 (0.8)
AC ... V
120
Hz
60
Amp
10
W
5
DC ... V
15
Amp
5 AF, ceramic, filled
with sand
° F ( °C)
32 ... 212
(0 ... 100)
° F ( °C)
– 40 ... 122
( – 40 ... 50)
° F ( °C)
32 ... 122
(0 ... 50)
° F ( °C)
32 ... 212
(0 ... 100)
° F ( °C)
– 58 ... 212
( – 50 ... 100)
ft (m)
( Tab. 6, page 11)
ft (m)
( Tab. 7, page 11)
IEC 60730
II in accordance
with IEC 60730
Type 2
Details about the MCM10 module
2.6.3

Power connection parameters

1)
Pos.
Interface
A
Input
Power supply from the power
line or from the previous mod-
ule MCM10
B
Output
Power supply for additional
MCM10
C
Output
Pump
D
Output
Remote fault indication
E
Input
Supply temperature sensor
F
Input
Outdoor temperature sensor NTC ( Tab. 4)
G
Input
External switching contact
H
Input
Heating controls
(ON/OFF contact)
I
Input
Heating controls (propor-
tional interface)
J
2-wire BUS to the heating controller
(RC35, WM10, MM10)
K
2-wire BUS from the previous MCM10
module
L
2-wire BUS to the next MCM10 module
M
2-wire BUS to the heating appliance
Tab. 2 Power connection parameters
1) (
Fig. 12, page 19)
2.6.4
Measurement values supply temperature
sensor
Ω
°F ( °C)
68 (20)
12490
77 (25)
10000
86 (30)
8057
95 (35)
6531
104 (40)
5327
113 (45)
4369
122 (50)
3603
131 (55)
2986
Tab. 3 Measurement values supply temperature sensor
2.6.5
Measurement values outdoor temperature
sensor
Ω
°F ( °C)
– 4 ( – 20)
97070
5 ( – 15)
72929
14 ( – 10)
55330
23 ( – 5)
42315
32 (0)
32650
41 (5)
25388
Tab. 4 Measurement values outdoor temperature
sensor
2
120 V AC,
max. 10 Amp.
120 V AC,
max. 10 Amp.
120 V AC,
max. 250 W
zero volt,
max. 120 V,
2 Amp.
NTC ( Tab. 3)
Zero volt
24 V DC
0-10 V DC
Ω
°F ( °C)
140 (60)
2488
149 (65)
2083
158 (70)
1752
167 (75)
1481
176 (80)
1258
185 (85)
1072
194 (90)
917
203 (95)
788
Ω
°F ( °C)
50 (10)
19900
59 (15)
15708
68 (20)
12490
77 (25)
10000
86 (30)
8057
95 (35)
6531
5