Continuous beep for two seconds: you have
pressed the ON/OFF switch to restart the
inverter. The tension in the outlet will be
immediately present after the acoustic
signal.

Model with stand-by system

The inverters from the AJ 500-12 are
equipped with a stand-by system which is in
function when no load is connected. In that
situation the inverter is in low power
consumption mode.
The output tension is not continuously
present and the LED is blinking as long as
no load is detected.
The minimal load detected can be adjusted
between 1 and 20 W. In most cases this
adjustment
is
not
adjustment is made with a small screw
driver in the hole marked stand-by. This
adjustment is made with a small screw
This
necessary.
AJ V2.3
driver in the hole marked stand-by.
Adjusting the switching-on level is as
follows:
Switch off
devices; turn the Turning Knob to the
Left (counter-clockwise)until the LED is
blinking,
switch
ON
consuming device (i.e. Mobile phone
charger); turn the Turning Knob slowly
to the right until LED is lit continuously.
Check that the inverter will go back in
stand-by mode when you remove the
load. If not, this means that the load is
too small to be detected.
If the stand-by is not required, turn the
Knob fully to the right.
In the full counter clockwise position,
the sensibility is minimal (20 W). Do
not push on the screw driver.
NOTE: in this mode the output voltage
is intermittently present at the output
AJ
all
consuming
the
smallest
6/30