05-350 / 05-338

4 TECHNICAL DATA

4.1. Easywave modular receiver 2-channel dim controller 05-350
- 2 potentialfree relay contacts, unipolar N.O., 4A, 230V 50Hz, suited only for monophase
configurations, not for SELV circuits
- 2 control outputs 1/10VDC – 45mA (EN60929) for SELV
- 2 outputs can be switched independently of each other
- supply voltage 230V 50Hz
- DIN rail mounting only, width 72mm, 4 DIN
- Degree of protection IP20
- Can be used with all Easywave transmitters
- LED and local push button (select) with on/off function
- Up to 32 transmitters can be allocated to 1 receiver
- Each transmitter can be allocated a different function
Load table for 05-350
2 potentialfree relay contacts, single pole N.O., only for monophase power supply 4A, 230V
50Hz, for the make contact. The relay contacts may not be used in SELV circuits.
Switch-on current: max. 30A/5ms. Approx. 4 ECGs can be switched immediately (type
dependent). Make allowance for the switch-on current peak of the ECG. For switching larger
numbers a power relay has to be used.
Type of charge: ECG: electronic control gear (HF fluorescentballast, electronic transformers...)
Maximum load: 4A / 920VA