Insulation Test - Tecumseh SH4576Z Instructions D'utilisation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Series V-Z-W
3 phase D.O.L.
D.O.L. motor – ∆ connection for DOL starting
M8 nut - Tightening torque 15 Nm
Ref
Description
1
M8x25 tropicalised zinc screw
2
8x17 brass washer
3
Bars
4
Spacer
5
∆ base insulator
PWS /
6
Fast-On lug for

Insulation test

An insulation or dielectric rigidity test has already been done in the factory. If you need to re-do this test,
load the compressor with nitrogen or refrigerant gas and apply a maximum voltage of 1000V ac.
Never do the insulation test on a compressor drawing a vacuum. A vacuum is an excellent
conductor and can cause a corona effect (flash cluster) and immediately void the warranty.
Never apply a voltage directly to the thermistance terminals. A few volts are enough to damage it.
Ensure that the protection devices (INT69® Diagnose included) are acting on the main contactor in
order to cut the supply to the compressor directly.