Guardian LP or Natural Gas Heater

Relay

(AW325)
The relay is responsible for supply of power to the
motor, and has numbers adjacent to its male termi-
nals for reference of voltage received and supplied
for troubleshooting.
Refer to Fig. 20 and the following table for connec-
tion of wiring and voltage checks.
Terminal Function
2
120 volts from relay to motor
4
120 volts to relay from power supply
6
120 volts from relay to motor
8
120 volts to relay from power supply
0
120 volts from ignition controller
to relay for relay coil closure
1
Neutral for relay
If the relay is receiving 115 volts at terminal 0 from
the ignition control, along with incoming power
supply voltage on terminals 4 and 8, but voltage is
not supplied to the motor from terminals 2 and 6, the
relay is defective.
FIG. 20
2
0
4
6
1
8
Owner's Manual • Guardian
Burner Orifice and
Gas Control Valve
1. Remove the following:
-- Hose and sediment trap from heater.
-- Plastic bushing at gas inlet hole
(if applicable). See Fig. 21.
-- Screws from bracket at inlet of gas
control valve. See Fig. 21.
-- Burner retaining bolt from underside of
base. See Fig. 22.
2. Pivot the valve/manifold assembly as
necessary so orifi ce on manifold clears the
burner casting venturi port. See Fig. 23.
FIG. 21
SCREWS AT
VALVE INLET
FIG. 22
FIG. 23
GAS CONTROL VALVE
ORIFICE
BUSHING