Fault message
In an error situation the LED's on the front will flash and the alarm relay will be activated. If you push the top button in this situation you can see the
alarm report in the display.
There are two kinds of error reports - it can either be an alarm occurring during the daily operation, or there may be a defect in the installation.
A-alarms will not become visible until the set time delay has expired.
E-alarms, on the other hand, will become visible the moment the error occurs.
(An A alarm will not be visible as long as there is an active E alarm).
Here are the messages that may appear:
Code / Alarm text via data
communication
A1/--- High t.alarm
A2/--- Low t. alarm
A4/--- Door alarm
A5/--- Max hold time
A10/--- Inject prob.
A11/--- No Rfg. sel.
A13/--- High temp S6
A14/--- Low temp S6
A15/--- DI1 alarm
A16/--- DI2 alarm
A45/--- Standby mode
A59/--- Case clean
A74/--- AD fault
A75/--- AD Iced
A76/--- AD not defr.
E1/--- Ctrl. error
E6/--- RTC error
E20/--- Pe error
E23/--- S1 error
E24/--- S2 error
E25/--- S3 error
E26/--- S4 error
E27/--- S5 error
E28/--- S6 error
E37/--- S5 error B
---/--- Max Def.Time
On copying settings to or from a copying key with the functions o65 or o66 the following information may appear:
0: Copying is complete and OK
-4: The copying key is not mounted correctly
-5: Copying did not run correctly. Repeat copying
-6: Copying to the controller did not run correctly. Repeat copying
-7: Copying to the copying key did not run correctly. Repeat copying
-8: Copying is not possible. The order number or SW version does not match
-9: Communication error and timeout
-10: Copying is still in progress
(Information can be found in o65 or o66 a couple of seconds after copying has commenced.)
Data communication
The importance of individual alarms can be defined with a setting. The setting must be carried out in the group "Alarm destinations"
Settings from
Settings from
System manager
AKM (AKM destination)
High
1
Middle
2
Low
3
Log only
Disabled
20
Description
High temperature alarm
Low temperature alarm
Door alarm
The "o16" function is activated during a coordinated defrost
Control problem
No refrigerant selected
Temperature alarm. High S6
Temperature alarm. Low S6
DI1 alarm
DI2 alarm
Standby position (stopped refrigeration via r12 or DI input)
Case cleaning. Signal from DI input
Error in the adaptive defrost function
Evaporator is iced up. Reduction of air flow
Defrost of evaporator is not satisfactory
Faults in the controller
Change battery and check clock
Error on pressure transmitter Pe
Error on S1 sensor
Error on S2 sensor
Error on S3 sensor
Error on S4 sensor
Error on S5 sensor
Error on S6 sensor
Error on S5B sensor
Defrost stopped based on time instead of, as wanted, on temperature
Log
X
X
X
X
Instructions RI8LN452 © Danfoss 05/2008
Alarm relay
Non
High
Low-High
X
X
X
X
Send via
Network
X
X
X
Additional information:
Manual RS8EN
AK-CC 550