Indoor Unit Installation; Installation Room - CLIVET CRISTALLO IM1-XY Serie Manuel D'instructions Pour L'installation, L'utilisation Et L'entretien

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Installation
2.4

Indoor unit installation

2.4.1

Installation room

m
CAUTION
The
appliance
well-ventilated room, with a minimum surface
area that varies according to the amount of
refrigerant present.
To calculate the minimum area of the installation room,
proceed as described below:
– determine the total refrigerant charge (see section
"3.1.1 Refrigerant charge" of the outdoor unit
manual)
– identify the refrigerant charge value in the table
below and derive the respective minimum area
required for the installation room.
Refrigerant charge
[kg]
< 1.224
1.225
1.4
1.6
1.8
2.0
2.2
2.4
2.6
2.8
3.0
3.2
3.4
3.6
3.8
4.0
4.2
4.4
4.6
4.8
5.0
5.2
5.4
5.6
5.8
6.0
6.2
6.4
must
be
placed
in
Minimum surface
[m
]
2
-
1.43
1.87
2.44
3.09
3.81
4.61
5.49
6.44
7.47
8.58
9.76
11.0
12.4
13.8
15.3
16.8
18.5
20.2
22.0
23.8
25.8
27.8
29.9
32.1
34.3
36.6
39.1
Refrigerant charge
[kg]
6.6
6.8
7.0
a
7.2
7.4
7.6
7.8
7.956
The following information can help you choose a suitable
location for the indoor unit.
The installation location must have the following
characteristics:
– good air circulation
– ease of drainage
– the noise emitted by the unit must not disturb other
people
– stability and robustness - no exposure to vibration
– sufficient capacity to support the weight of the unit
– at least one metre away from any other electrical
device (e.g. TV, radio, computer)
d
It is PROHIBITED to install the indoor
unit in the following locations:
– near sources of heat, steam or combustible
gas;
– near flammable objects, such as curtains or
fabrics;
– near obstacles that could obstruct air
circulation;
– near the entrance;
– In a an area that is not exposed to direct
sunlight.
l
NOTE ON THE HOLE IN THE WALL
If there is no fixed refrigerant piping:
When choosing the installation position, it
is recommended to provide a sufficiently
large space for the wall hole (see paragraph
"2.4.3 Preparation for connection pipes") in which
to insert the signal cable and the refrigerant
piping between the indoor and outdoor units.
The usual position for cables and pipes is on the
right side of the indoor unit (looking at the unit).
However, the unit supports installation of cables
and piping both on the left and on the right.
Minimum surface
[m
]
2
41.5
44.1
46,7
49.4
52.2
55.1
58.0
61.0