mundoclima 2022 Manuel page 84

Codes d'erreurs
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

SERIES:
OUTDOOR UNITS MINI MVD V4+ (8 - 18 kW)
UNITS:
MVD-V120W/DRN1
MVD-V140W/DRN1
MVD-V160W/DRN1
MVD-V180W/DRN1
Code
HF
Electronic incompatibility between indoor and outdoor unit
E0
EEPROM fault
E9
E2
Communication malfunction between indoor and outdoor
E3
Communication malfunction between main PCB and inverter
H0
E4
T3 and/or T4 sensor fault
E5
Voltage protection
E6
DC fan motor fault
E7
Sensor value more than 27ºC during 5 minutes in heating mode
EA
E8
E6 fault displayed twice in 10 min
Eb
P0
Reserved
P1
High pressure protection
P2
Low pressure protection
P3
Overcurrent protection
P4
High temperature protection in the compressor discharge T5
P5
High condensation temperature protection T3
P6
Inverter module protection
P7
High evaporation temperature protection T2
PE
P8
Typhoon protection
L0
Inverter module fault
L1
Low voltage protection DC
L2
High voltage protection DC
L3
Reserved
L4
MCE fault
L5
Zero speed protection
L6
Reserved
L7
Phases fault
L8
Frequency increased more than 15Hz in 1 s.
L9
Frequency difference between current and the main command more than
Note: P6 code is displayed, to know the fault detail (L*) please push SW2 until last memorized fault
code parameter is extracted.
Error details P6
LED1
8 flashes
9 flashes
10 flashes
(CL23265)
(CL23266)
(CL23267)
(CL23268)
Description
LED2
ON
ON
ON
84
TROUBLESHOOTING
(CL23260 to CL23268)
Specific code
Inverter module fault
Low voltage protection
High voltage protection
EN
Applicable
Only 18KW
12 - 16 KW
Only 18KW
All
12 - 16 KW
Only 18KW
All
All
All
12 - 16 KW
Only 18KW
12 - 16 KW
Only 18KW
- -
All
All
All
All
All
All
12 - 16 KW
Only 18KW
All
Only 18KW
Only 18KW
Only 18KW
Only 18KW
Only 18KW
Only 18KW
- -
Only 18KW
Only 18KW
Only 18KW